Calculations DIN EN ISO 13849-1 Performance Level - low voltage 230 V
Calculations DIN EN ISO 13849-1 Performance Level - extra low voltage (ELV) 24 V
3. The MTTF
d
value of a partial system must be limited to 100 years according to the DIN EN ISO 13849-1 requirements.
Variant
MTTF
d
DC
avg
CCF
PL
1
100 years
3
(337 years)
90 %
80
PLd
1a
100 years
3
(337 years)
90 %
80
PLe
2
100 years
3
(340 years)
90 %
80
PLe
3
100 years
3
(317 years)
91 %
80
PLe
4
100 years
3
(313 years)
91 %
80
PLe
5
100 years
3
(327 years)
91 %
80
See "Connection possibilities of
the sensors" table
Variant
MTTF
d
DC
avg
CCF
PL
1
100 years
3
(336 years)
90 %
80
PLd
1a
100 years
3
(336 years)
90 %
80
PLe
2
100 years
3
(339 years)
90 %
80
PLe
3
100 years
3
(315 years)
90 %
80
PLe
4
100 years
3
(311 years)
90 %
80
PLe
5
100 years
3
(318 years)
90 %
80
See "Connection possibilities of
the sensors" table