Page 12/14

Data Sheet 701150

2012-07-01/00540116

JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14

36039 Fulda, Germany

Postal address:

36035 Fulda, Germany

Phone:

+49 661 6003-0

Fax:

+49 661 6003-607

E-mail:

[email protected]

Internet:

www.jumo.net

JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax:

+44 1279 635262

E-mail:

[email protected]

Internet: www.jumo.co.uk

JUMO Process Control, Inc.
8 Technology Boulevard
Canastota, NY 13032, USA
Phone: 315-697-5866

1-800-554-JUMO

Fax:

315-697-5867

E-mail:

[email protected]

Internet: www.jumousa.com

Calculations DIN EN ISO 13849-1 Performance Level - low voltage 230 V

Calculations DIN EN ISO 13849-1 Performance Level - extra low voltage (ELV) 24 V

3. The MTTF

d

value of a partial system must be limited to 100 years according to the DIN EN ISO 13849-1 requirements.

Variant

MTTF

d

DC

avg

CCF

PL

1

100 years

3

(337 years)

90 %

80

PLd

1a

100 years

3

(337 years)

90 %

80

PLe

2

100 years

3

(340 years)

90 %

80

PLe

3

100 years

3

(317 years)

91 %

80

PLe

4

100 years

3

(313 years)

91 %

80

PLe

5

100 years

3

(327 years)

91 %

80

See "Connection possibilities of
the sensors" table

Variant

MTTF

d

DC

avg

CCF

PL

1

100 years

3

(336 years)

90 %

80

PLd

1a

100 years

3

(336 years)

90 %

80

PLe

2

100 years

3

(339 years)

90 %

80

PLe

3

100 years

3

(315 years)

90 %

80

PLe

4

100 years

3

(311 years)

90 %

80

PLe

5

100 years

3

(318 years)

90 %

80

See "Connection possibilities of
the sensors" table