5 Settings

36

IGBT Power Converter 200A [Patent No. EP1 126 591 B1] 02.08

5.6 Firing pulse inhibit

The firing pulse inhibit function provides a simple way of switching
to high power levels.

A contact between connections 6 and 7 can be used to switch off the load.
The external contact can be a make or break contact, depending on the
position of S105.

k

factory setting

Factory setting

S105 is in position 1

5.7 Resistance output

When the converter is operating within rated limits, the resistance output has a
voltage of 4 ... 5 V.

V

In order to be able to disconnect a system from the supply voltage,
a circuit-breaker or main switch for all-pole disconnection must be
wired into the supply feed!

A

If the output power is simply removed by inhibiting the firing
pulses, this does not provide electrical isolation from the voltage
supply! The terminals D or 1D may still carry dangerous voltage
from the supply.

External contact

Internal switch S105

Response

Make (a)

Position 1

The load is permanently
switched off when the contact
is closed

Break (b)

Position 2

The load is permanently
switched off when the contact
is open