3 Installation

14

IGBT Power Converter 200A [Patent No. EP1 126 591 B1] 02.08

The earth leakage current of the IPC power converter with a filter wired into the
supply lead is less than 3 mA. If the load conditions result in an earth leakage
current greater than 3.5 mA, a fixed supply connection is required as a
protection against hazardous potentials (also see EN 50178).

Electromagnetic compatibility conforms to the standards and regulations cited
in the technical data.

v Chapter 6 „Technical data“
h Load wiring (thick) and cables for control inputs (thin) should be routed

separately, if possible.

H

The EMC filters may only be used for interference suppression of the
IPC power converter. Other devices, such as controllers, power
supplies etc. must be suppressed, where necessary, with their own
EMC filters. Do not wire these devices in parallel to the IPC power
converter on the load side of the EMC filter.