WARNING

Follow all local electrical and safety codes, as well

as the National Electrical Code (NEC) and the

Occupational Safety and Health Act (OSHA).

This product contains chemicals known to the State of

California to cause cancer and birth defects or other

reproductive harm.

Do not use to pump flammable or explosive fluids

such as gasoline, fuel oil, kerosene, etc. Do not use

in flammable and/or explosive atmospheres.

Install pressure relief valve in discharge pipe.

Release all pressure on system before working on

any component.

CAuTION

Wire motor for correct voltage. See Electrical section

and motor nameplate.

Ground motor and controls before connecting to

power supply.

Follow wiring instructions in this manual when

connecting to power lines.

Protect power cable from nicks or cuts from sharp

objects or scraping on well casing when lowering

pump into well. Do not allow it to come into contact

with oil, grease, hot surfaces or chemicals.

The motor voltage and phase indicated on the motor

nameplate should be checked against the actual

electrical supply. Check your power source. Check

electrical supply for correct fusing, wire size, and

adequate grounding and transformer size.

The power supply for a submersible pump should be

a separate circuit, independent of all other circuits. It

must be equipped with a fuse box of ample capacity.

Shut off power source when voltage drops 10% below

rated voltage of motor.

For fire protection, power supply should be free of any

building, preferably on a direct line from transformer.

In event of fire, wires will not be destroyed and water

supply not cut-off.

SAFETY INFORMATION

NOTE: Install all electrical equipment in protected area to provide adequate ventilation for pressure switch and

controls to prevent moisture damage to components.
NOTE: Install pump, pressure tank, pitless adaptor or well seal in accordance with state and local plumbing

codes.

PREPARATION

Before beginning installation of product, make sure

all parts are present. Compare parts with package

contents drawing. If any part is missing or damaged,

do not attempt to assemble the product. Contact

customer service for replacement parts.

SubMERSIblE PuMP CAblE ANd POwER

CAblE SElECTION
Check cable size against Submersible Wire Size

Chart A. For 3-wire plus ground models, motor

and control box voltage must match. Submersible

power cable must be UL listed for submersible pump

applications. For Canadian installations, type RWU,

TWU, SGOW or SWOW power supply cable is

recommended. Cable is selected for the maximum

pump setting plus the offset distance to the service

entrance.
IMPORTANT: Use of wire sizes smaller than those

specified in the chart will cause low starting voltage,

may cause early pump failure and will void the

warranty. Larger wire sizes may always be used

for better economy of operation. Be sure voltage

at pressure switch or fuse is between the following

limits:
115V Rated - Between 104 & 127 volts
230V Rated - Between 210 & 250 volts
The National Electric Code (NEC 250-43) requires

a separate ground wire be run down the well to the

submersible pump and connected to all exposed

metal parts of the pump and motor. Refer to the

most recent National Electric Code (NEC) Article 250

(grounding) for additional information.
NOTE: All wiring should be done by a qualified

electrician.

wARNING: 3-wIRE SubMERSIblES ONlY: This submersible pump must be wired

directly to a control box of the same horsepower and voltage rating in order to work properly.

IT MuST bE uSEd wITH wITH A CONTROl bOX.

HP

Volt

Maximum Cable length In Feet using AwG Cable*

#14

#12

#10

1/2

110/115

100

160

250

1/2

230

400

650

1020

3/4

230

300

480

760

1

230

250

400

630

1-1/2

230

190

310

480

2

230

150

250

390

3

230

120

190

300

*

NOTE: Wire length is the total distance from power source to pump depth.

wire Size Chart A