Flint & Walling 4 (10 cm) Stainless Commander S Series User Manual
Page 10

18
Copyright © 2014 Flint & Walling. All rights reserved.
19
Copyright © 2014 Flint & Walling. All rights reserved.
ElECTRICAl HOOKuP FROM THE HOuSE TO PuMP ANd PRESSuRE TANK
10. Thread the cable from the house electrical
service through one of the holes in the side
of the pressure switch and tighten down the
electric wire strain relief.
CAuTION: Do not crush wire. (Fig. 10)
11. Connect the two wires from the house electrical
service to the outside pressure switch terminals
(L1 and L4).
(Fig. 11)
ElECTRICAl HOOKuP FROM THE HOuSE TO PuMP ANd PRESSuRE TANK
12. Thread the cable from the control box through
the remaining hole in the side of the pressure
switch and tighten down the electric wire strain
relief.
CAuTION: Do not crush wire. (Fig. 12)
13. Connect the two wires from the control box to
the inside pressure switch terminals (L2 and
L3).
(Fig. 13)
14. Connect green ground wires from the control
box cable and the house electric cable to the
two ground screws on base of pressure switch.
Replace switch cover.
(Fig 14)
IL1162
L4
L1
Strain Relief
L4
L1
L4
L1
10
11
IL1165
12
L3
L2
IL1167
L2
L3
13
IL1182
Ground Screws
From
Control Box
From
Power Source
14
TROublESHOOTING
Problem
Possible Cause
Corrective Action
Fuses blow
1. Incorrect voltage at motor
1. Check for correct wire size. Replace
undersize wire. Check line voltage,
contact power company if voltage is
incorrect
2. Defective fuse box or incorrect fuses
2. Inspect fuse box wiring and correct.
Install the proper fuses
3. Defective pressure switch
3. Replace pressure switch or clean
contacts
4. Control box malfunction
4. See control box checking and repairing
procedures. Replace defective
components
5. Defective drop cable insulation
5. Check drop cable insulation resistance.
Pump must be pulled to replace
defective cable
6. Motor malfunction
6. Check motor winding resistance. Pump
must be pulled to replace defective
motor
7. Pump malfunction
7. If all above checks are good, then pump
is probably bound. Pump must be
pulled. Check for sand or pump shaft
misalignment. Correct well condition if
sand is the problem
Motor won’t start.
Fuses don’t
blow
1. No power to start motor
1. Check voltage at line side of fuse box.
Contact power company if no power is
reaching box. Check voltage at load
side of fuse box and at other control
devices in circuit. Make necessary
corrections
2. Defective drop cable or motor
2. Check motor winding resistance. Pump
must be pulled to replace defective
cable or motor