Connecting the Cables

.7.1 Wiring the Trio

Once the Trio is mounted, you are ready to wire the device. Proper wiring, grounding and

shielding are essential for ensuring safe, immune and optimal servo performance of the Trio.

Follow these instructions to ensure safe and proper wiring

Use twisted pair shielded cables for control, feedback and communication connections. For

best results, the cable should have an aluminum foil shield covered by copper braid, and

should contain a drain wire.

The drain wire is a non-insulated wire that is in contact with parts of the cable, usually the shield.

It is used to terminate the shield and as a grounding connection.

The impedance of the wire must be as low as possible. The size of the wire must be thicker

than actually required by the carrying current. A 26 or 28 AWG wire for control and

feedback cables is satisfactory although 26 AWG is recommended.

Use shielded wires for motor connections as well. If the wires are long, ensure that the

capacitance between the wires is not too high: C < 30 nF is satisfactory for most

applications.

Keep all wires and cables as short as possible.

Keep the motor wires as far away as possible from the feedback, control and

communication cables.

Ensure that in normal operating conditions, the shielded wires and drain carry no current.

The only time these conductors carry current is under abnormal conditions, when electrical

equipment has become a potential shock or fire hazard while conducting external EMI

interferences directly to ground, in order to prevent them from affecting the drive. Failing

to meet this requirement can result in drive/controller/host failure.

After completing the wiring, carefully inspect all wires to ensure tightness, good solder

joints and general safety.


The following connectors are used for wiring the Trio:

Type

Function

Connector Location

Main Power

PE, AC2, AC1,

VP+, PR, PR, VL

Motor Power

PE, M3, M2, M1

Table

3-1: Connectors on the “Bottom” of the Trio

Main Power

Motor

Power