beautypg.com

Gold drum power supply connections, Multiple connections topology – ElmoMC Gold Line Digital Servo Drives-Gold Drum Ver 1_400 RJ-45 connectors User Manual

Page 28

background image

Gold Drum (RJ-45 Connectors) Installation Guide

MAN-G-DRUM(RJ45)IG-EC (Ver. 1.400)

||Main Power|

www.elmomc.com

28

Table of Contents

9.5.1.1.

Gold Drum Power Supply Connections

Figure 11: Non-Isolated from the Mains DC Power Supply connection

Figure 12: Isolated from the Mains DC Power Supply connection

Important Notice

In the Isolated connection the G-DRU VN- terminal MUST be connected to the "Earth
Connection" (marked in red in Figure 12 above).

In the Non Isolated Connection ( direct to Mains) the VN- terminal MUST NOT be connected to

"Earth Connection"(PE) (Figure 11).

9.5.1.2.

Multiple Connections Topology

In a multi-axis application it is likely that a single power supply can feed several drives in parallel.
The power supply is connected directly to the mains AC line and it feeds more than one drive.

This topology is efficient and cost saving, by reducing the number of power supplies and the
amount of wiring. Most importantly it utilizes an energy sharing environment among all the drives
that share the same DC bus network.