- Electrically operate the actuator in the open direction until the actuator stops
- Exit setup mode (move switch SW3 to position 1) or proceed to the next step:



Stroke time setting – closing direction of travel

Important: Refer to Actuator Default Settings above.


To modify the default setting, proceed as follows:

- Enter setup mode: move switch SW3 to the ON position
- Rotate switch SW4 to position 4
- Rotate switch SW6 to: positions 0-9. Choose the required stroke time from the STROKE TIME

SELECTION TABLE below.

- Confirm by pushing ENTER pushbutton SW5
- When pushing SW5, the red LED will blink once to confirm that the setting is accepted
- Exit setup mode (move switch SW3 to position 1) or proceed to the next step:

Model

Nominal

Torque

(Lbs-inches)

Operating Time (sec/90°) at selected step*

9

8

7

6

5

4

3

2

1

0

E6

600

12

15

18

26

38

48

60

75

85

110

E13

1300

12

15

18

26

38

48

60

75

85

110

E25

2500

12

15

18

26

38

48

60

75

85

110

E51

5100

12

15

18

26

38

48

60

75

85

110

E91

9100

20

24

30

45

60

80

100

120

140

180

E171

17100

44

53

66

100

132

180

220

264

310

400

*Times are +/- 10% tolerance for a 90° stroke.



Stroke time setting – opening direction of travel

Important: Refer to Actuator Default Settings above.


To modify the default setting, proceed as follows:

- Enter setup mode: move switch SW3 to the ON position
- Rotate switch SW4 to position 5
- Rotate switch SW6 to: positions 0-9. Choose the required stroke time from the STROKE TIME

SELECTION TABLE above.

- Confirm by pushing ENTER pushbutton SW5
- When pushing SW5, the red LED will blink once to confirm that the setting is accepted
- Exit setup mode (move switch SW3 to position 1) or proceed to the next step