- Electrically operate the actuator in the open direction until the actuator stops
- Exit setup mode (move switch SW3 to position 1) or proceed to the next step:
Stroke time setting – closing direction of travel
Important: Refer to Actuator Default Settings above.
To modify the default setting, proceed as follows:
- Enter setup mode: move switch SW3 to the ON position
- Rotate switch SW4 to position 4
- Rotate switch SW6 to: positions 0-9. Choose the required stroke time from the STROKE TIME
SELECTION TABLE below.
- Confirm by pushing ENTER pushbutton SW5
- When pushing SW5, the red LED will blink once to confirm that the setting is accepted
- Exit setup mode (move switch SW3 to position 1) or proceed to the next step:
Model
Nominal
Torque
(Lbs-inches)
Operating Time (sec/90°) at selected step*
9
8
7
6
5
4
3
2
1
0
E6
600
12
15
18
26
38
48
60
75
85
110
E13
1300
12
15
18
26
38
48
60
75
85
110
E25
2500
12
15
18
26
38
48
60
75
85
110
E51
5100
12
15
18
26
38
48
60
75
85
110
E91
9100
20
24
30
45
60
80
100
120
140
180
E171
17100
44
53
66
100
132
180
220
264
310
400
*Times are +/- 10% tolerance for a 90° stroke.
Stroke time setting – opening direction of travel
Important: Refer to Actuator Default Settings above.
To modify the default setting, proceed as follows:
- Enter setup mode: move switch SW3 to the ON position
- Rotate switch SW4 to position 5
- Rotate switch SW6 to: positions 0-9. Choose the required stroke time from the STROKE TIME
SELECTION TABLE above.
- Confirm by pushing ENTER pushbutton SW5
- When pushing SW5, the red LED will blink once to confirm that the setting is accepted
- Exit setup mode (move switch SW3 to position 1) or proceed to the next step