Elkhart Brass 70133000 Electric Valves User Manual
Page 20
20
ACTUATOR SETUP
WARNING: Settings must be performed with power to the actuator energized. Ensure settings
are carried out by qualified personnel.
Actuator Default Settings
- Closed direction of travel, Position seating
- Open direction of travel, Position seating
- Stroke time: 15 seconds for models 006, 013, 025 and 051
30 seconds for model 091
66 seconds for model 171
- Closing torque set at 100% of rated torque
- Opening torque set at 100% of rated torque
- Reverse mode off.
If the application requires different actuator settings, please proceed as described later in this chapter.
Important: Setting modifications can be performed in any sequence. All parameters can be set
independently.
Modifications to the actuator’s settings are done using the following components inside the actuators controls
enclosure:
- Two rotary selector switches SW6 and SW4
- Enter push-button SW5 (confirmation push-button)
- Dip-switch SW3 (enter setup mode)
- Green LED, Power On indication (switched on when power supply is available)
- Red LED for Enter confirmation (Blinks once to confirm the setting is accepted)