Det-Tronics MOS H2S Gas Sensor User Manual
Page 4

95-8532
1.4
2
DETECTION RANGE—
0 to 100 ppm
RELAY CONTACTS (OPTIONAL)—
Three Alarm relays: Form C, 5 amperes at 30 vdc.
Selectable normally energized or de-energized as a
group; low and auxiliary alarm selectable together for
latching or non-latching contacts, high alarm contacts
are always latching.
One Fault relay: Form C, 5 amperes at 30 vdc. Normally
energized for no fault condition with power applied to
device.
TEMPERATURE RANGE—
Operating: –40°F to +167°F (–40°C to +75°C).
Storage:
–67°F to +185°F (–55°C to +85°C).
WIRING—
18 AWG minimum is recommended for power wiring to
the transmitter. Larger diameter wire may be required
to maintain a minimum of 16 vdc at the transmitter for all
operating conditions. Maximum wire size for terminals is
12 AWG.
CERTIFICATION—
CSA:
Class I, Div. 1, Groups B, C, and D;
Class I, Div. 2, Groups A, B, C and D (T4A)
Tamb = –40°C to +75°C.
CENELEC/CE: 0539 II 2 G
EEx d IIC T5-T6
DEMKO 02 ATEX 131327X
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –55°C to +75°C)
IP66.
ENCLOSURE MATERIAL—
Epoxy coated 356 alloy aluminum or 316 stainless steel.
(Standard with two conduit entries.)
DIMENSIONS—
See Figure 1A.
SHIPPING WEIGHT
(Transmitter and Junction Box)—
Aluminum:
4.15 pounds (1.88 kilograms).
Stainless steel: 10.5 pounds (4.76 kilograms).
Sensor
RESPONSE TIME—
T50 < 60 seconds.
ACCURACY (LINEARITY)—
±12 ppm.
TEMPERATURE RANGE—
Operating: 32°F to +167°F (0°C to +75°C).
Storage:
–67°F to +257°F (–55°C to +125°C).
zERO STABILITY—
±1 ppm over one year.
CALIBRATION CYCLE—
30 days.
CERTIFICATION—
CSA:
Class I, Div. 1, Groups B, C and D;
Class I, Div. 2, Groups A, B, C and D;
Tamb = –40°C to +75°C.
CENELEC/CE: 0539 II 2 G
EEx d IIC T4
DEMKO 03 ATEX 135937X
T4 (Tamb = –40°C to +70°C).
DIMENSIONS—
See Figures 1B and 1C.
WARRANTY—
2 years.
3.46
(8.8)
4.7
(11.9)
2.7
(6.9)
5.2
(13.2)
5.86
(14.9)
6.57
(16.7)
1.28
(3.3)
A2307
Figure 1A—Infiniti Transmitter Dimensions in Inches (Centimeters)
FM
®