Det-Tronics MOS H2S Gas Sensor User Manual
Page 13

95-8532
1.4
11
Setpoints
The Infiniti Transmitter has three independent alarm
outputs (low, high and auxiliary), with field selectable
setpoints. For both relay and non-relay models, these
setpoints correspond to the HI, AUX, and LO ALARM
indicators on the display.
Calibration Gas Concentration
The calibration gas concentration is displayed but is not
adjustable. The Det-Tronics 40 ppm Ampoule Calibration
Kit should be used to ensure proper calibration.
IMPORTANT
40 ppm H
2
S in air must be used for calibrating the
MOS H
2
S sensor. Compressed H
2
S gas cylinders
are not recommended.
Latching or Non-latching Relays
The Low and Auxiliary alarm relays are programmable
as a group for either latching or non-latching operation.
“LATCH” indicates that they will latch upon alarm and the
unit must be reset to clear. “nonLATCH” indicates that
they will automatically clear when the alarm clears. The
High alarm relay is always latching.
alarm Relays Normally Energized or Normally
De-Energized
The three alarm relays (High, Low and Auxiliary) are
programmed as a group. “DE-ENERG” indicates that
the three alarm relays will be normally de-energized and
will energize upon alarm. “ENERG” indicates that the
three alarm relays will be normally energized and will de-
energize upon alarm.
External Calibration
Calibration procedures are normally initiated and
executed using the Cal Magnet to activate the CAL/
RESET switch. Choose “EXTCAL YES” during the setup
procedure to allow the additional use of the external reset
input terminal for initiating and executing a calibration
procedure.
4-20 Milliampere Calibration
The 4 to 20 ma current loop is factory calibrated. Perform
the “4-20 CAL YES” function in the Setup procedure if a
current loop output other than 4 to 20 ma is required. The
calibrated 4 to 20 ma output remains linear.
Calibration Current
The current output during Calibration and while in the
Setup mode is factory set for 2 ma. Perform the “SET
CAL CURRENT” function in the Setup procedure if an
output current other than 2 ma is required.
Refer to the “Setup Procedure” section for complete
instructions.
INfINITI OUTpUTS
Refer to Table 3 for a description of Infiniti standard 4 to
20 ma outputs and relay output programming options.
MODES OF OPERATION
Refer to Table 4 for a description of Infiniti modes of
operation.