beautypg.com

Det-Tronics MOS H2S Gas Sensor User Manual

Page 22

background image

95-8532

1.4

20

MAINTENANCE

A routine maintenance schedule is recommended to

ensure that the detector is in peak operating condition at

all times. To ensure top performance, service the device

as follows.

VISUaL INSpECTION
A visual inspection of the detector approximately once

per week is recommended to ensure that physical

obstructions such as trash, debris, mud, snow, or oil

have not blocked or impeded hazardous gas access to

the sensor. This includes visually inspecting the sintered

metal filter on the sensor.

RESpONSE TEST
It is acceptable to perform a detector response

verification test in lieu of a complete calibration if the

detector output in clean air appears stable and the

device has been calibrated recently. This test involves

simply applying calibration gas to the detector while in

normal operating mode and confirming that the detector

output is proportional to the applied gas concentration.

It is the operator’s responsibility to bypass any and all

system alarm output devices, if necessary, prior to

conducting the detector response test. If the response

test results are not acceptable, a complete calibration

must be performed.

NOTE

Fault detection circuitry continuously monitors
for problems that could prevent proper system
response. It does not monitor external response
equipment or the wiring to these devices. It is
important that these devices be checked initially
when the system is installed, as well as periodically
during the ongoing maintenance program.

The system must be checked periodically in
the Normal mode to ensure that those items not
checked by the transmitter diagnostic circuitry
(such as output relays) are functioning properly.

CaLIbRaTION
Calibrate the detector following the schedule in the

“Calibration” section of this manual.

SINTERED METaL fILTER
H

2

S gas enters the sensor through the sintered metal

filter on the front of the sensor housing. A dirty filter can

significantly reduce the amount of H

2

S gas that is able to

reach the sensing element, thereby impairing the ability

of the system to respond to a hazardous condition. If the

filter becomes dirty and cannot be properly cleaned or if

it is damaged, the sensor must be replaced.

NOTE

If the detector cannot be calibrated or responds
slowly to the calibration gas, check the condition of
the filter before replacing the sensor.

SENSOR REpLaCEMENT
The MOS sensor is not field repairable. If calibration can

no longer be properly performed, the sensor must be

replaced.

The area must be de-classified or power to the detector

should be removed prior to replacing the sensor in a

hazardous area.

Follow the procedure below to replace the sensor.

Remove power to the transmitter prior to replacing

1.

the sensor.
Remove the transmitter cover and the wire shield

2.

within the transmitter.
Unplug the sensor from the transmitter module and

3.

unscrew it from the conduit entry.
Thread the wires for the replacement sensor through

4.

the conduit entry, then screw the sensor into the

conduit entry and plug it in. Replace the wire

shield.
Replace the junction box cover.

5.

Re-apply power. Allow time for the unit to warm

6.

up and stabilize (approximately 24 hours for best

results), then calibrate.

An adequate supply of spare sensors should be kept

on hand for field replacement. For maximum protection

against contamination and deterioration, they should not

be removed from the original protective packaging until

the time of installation. To ensure maximum storage life,

sensors should be stored at a temperature between 32°F

and 68°F (0 to 20°C) and a relative humidity between

15 and 90 percent. Always calibrate after replacing the

sensor.