Appendix b, Csa approval – Det-Tronics X3302 Multispectrum IR Flame Detector User Manual
Page 31
29
95-8576
9.2
APPENDIX B
CSA AppROvAL
Multispectrum IR Flame Detector/Controller X3302 Series, rated 18-30 Vdc, 4.6 Watts to 17 Watts.
Relay contacts rated 30 Vdc, 5 Amps.
NOTE
Hazardous location testing has been successfully completed on the Model X3302 series from an ambient
temperature range of –55°C to +125°C; however, the detector label marking indicates –40°C to +75°C.
The following accessories are CSA approved for use with the X3302 Flame Detector:
part Number
Description
102740-002
Magnet
007739-001
Magnet and Extension Pole
010857-001
Q1130A1001 Flange Mount Assembly
007290-001
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
007290-002
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
011385-001
Q9033 Collar Attachment
DIvISION CLASSIFICATION:
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Class I, Division 1, Groups B, C, and D (T4A); Class II, Division 1, Groups E, F, and G (T4A);
Class I, Division 2, Groups A, B, C, and D (T3C); Class II, Division 2, Groups F and G (T3C);
Class III; Enclosure NEMA/Type 4X;
Conduit seal not required.
ZONE CLASSIFICATION:
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Ex d e IIC T5-T6
T6 (Ta –50
o
C to +60
o
C)
T5 (Ta –50
o
C to +75
o
C)
Seal required adjacent to enclosure
IP66/IP67.
Ex d IIC T4-T6
T6 (Ta –55
o
C to +60
o
C)
T5 (Ta –55
o
C to +75
o
C)
T4 (Ta –55
o
C to +125
o
C)
Seal required adjacent to enclosure
IP66/IP67.
AppLICABLE REQUIREMENTS
CSA Std C22.2 No. 25-1966
– Enclosures for use in Class II Groups E, F & G Hazardous Locations
CSA Std C22.2 No. 30-M1986
– Explosion-Proof Enclosures for use in Class I Hazardous Locations
CAN/CSA C22.2 No. 94-M91
– Special Purpose Enclosures
CSA Std C22.2 No. 142-M1987
– Process Control Equipment
CSA Std C22.2 No. 213-M1987
– Nonincendive Electrical Equipment for use in Class I, Division 2 Hazardous Locations
AppLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 60079-0:07 – Electrical apparatus for explosive gas atmospheres. Part 0: General requirements
CAN/CSA-C22.2 No. 60079-1:11 – Explosive atmospheres. Part 1: Equipment protection by flameproof enclosures "d"
CAN/CSA-C22.2 No. 60079-7:12 – Explosive atmospheres. Part 7: Equipment protection by increased safety "e"