High resolution field of view, Fm approval and performance report – continued – Det-Tronics X3302 Multispectrum IR Flame Detector User Manual
Page 29
27
95-8576
9.2
hIgh RESOLUTION FIELD OF vIEW
0°
15°
30°
45°
15°
30°
45°
0°
15°
45°
15°
30°
30°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
100 (30.5)
90 (27.4)
80 (24.4)
70 (21.3)
60 (18.3)
50 (15.2)
40 (12.2)
30 (9.1)
20 (6.1)
10 (3)
10 (3)
20 (6.1)
30 (9.1)
40 (12.2)
50 (15.2)
60 (18.3)
70 (21.3)
80 (24.4)
90 (27.4)
100 (30.5)
Field of View at Indicated Distance in Feet (m) for
hydrogen at
very high Sensitivity (30 inch plume, with 100 SLPM flow rate)
0°
15°
15°
30°
45°
30°
45°
75
(22.9)
65 (19.8)
55 (16.8)
45 (13.7)
35 (10.7)
25 (7.6)
15 (4.6)
15
(4.6)
25 (7.6)
35 (10.7)
45 (13.7)
55 (16.8)
65 (19.8)
75 (22.9)
0
°
15
°
45
°
15
°
30
°
30
°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
Field of View at Indicated Distance in Feet (m) for
hydrogen at
high Sensitivity (30 inch plume, with 100 SLPM flow rate)
0°
15°
45°
15°
30°
30°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
0°
15°
15°
30°
45°
30°
45°
70
(21.3)
60 (18.3)
50 (15.2)
40 (12.2)
30 (9.1)
20 (6.1)
10 (3)
10
(3)
20 (6.1)
30 (9.1)
40 (12.2)
50 (15.2)
60 (18.3)
70 (21.3)
Field of View at Indicated Distance in Feet (m) for
Methanol at very high Sensitivity (1 x 1 ft)
0°
15°
45°
15°
30°
30°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
15°
30°
45°
15°
30°
45°
0°
52.5 (16)
50 (15.2)
45 (13.7)
40 (12.2)
35 (10.7)
30 (9.1)
25 (7.6)
20 (6.1)
15 (4.6)
10 (3)
5 (1.5)
5 (1.5)
10 (3)
15 (4.6)
20 (6.1)
25 (7.6)
30 (9.1)
35 (10.7)
40 (12.2)
45 (13.7)
50 (15.2)
52.5 (16)
Field of View at Indicated Distance in Feet (m) for
Methanol at high Sensitivity (1 x 1 ft)
FM Approval and performance Report – Continued