Det-Tronics X3302 Multispectrum IR Flame Detector User Manual
Page 25
23
95-8576
9.2
FM Approval and performance Report – Continued
NOTE
Refer to the “High Resolution Field of View” charts (page 27) for additional information.
FIELD OF vIEW
very high Sensitivity
Fuel
Size/
Flow Rate
Distance
feet (m)
horizontal
(degrees)
Avg. horiz.
Response Time
(seconds)**
vertical
(degrees)
Avg. vert.
Response Time
(seconds)**
Hydrogen
30 inch plume/
100 SLPM*
100 (30.5)
+45
-45
2
2.5
+45
-30
8
1.5
Methanol
1 x 1 foot
70 (21.3)
+45
-45
10
6
+45
-30
8.5
6
* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).
** Add 2 seconds for EQP model.
high Sensitivity
Fuel
Size/
Flow Rate
Distance
feet (m)
horizontal
(degrees)
Avg. horiz.
Response Time
(seconds)**
vertical
(degrees)
Avg. vert.
Response Time
(seconds)**
Hydrogen
30 inch plume/
100 SLPM*
75 (22.9)
+45
-45
4
2.5
+45
-30
3
3
Methanol
1 x 1 foot
52.5 (16.0)
+45
-45
4.5
3.5
+45
-30
4.5
2.5
* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).
** Add 2 seconds for EQP model.
Medium Sensitivity
Fuel
Size/
Flow Rate
Distance
feet (m)
horizontal
(degrees)
Avg. horiz.
Response Time
(seconds)**
vertical
(degrees)
Avg. vert.
Response Time
(seconds)**
Hydrogen
30 inch plume/
100 SLPM*
50 (15.2)
+45
-45
4.5
3.5
+45
-30
3
5
Methanol
1 x 1 foot
35 (10.7)
+45
-45
9.5
6
+45
-30
10.5
5.5
* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).
** Add 2 seconds for EQP model.
Low Sensitivity
Fuel
Size/
Flow Rate
Distance
feet (m)
horizontal
(degrees)
Avg. horiz.
Response Time
(seconds)**
vertical
(degrees)
Avg. vert.
Response Time
(seconds)**
Hydrogen
30 inch plume/
100 SLPM*
25 (7.6)
+45
-45
2
2.5
+45
-30
2.4
2
Methanol
1 x 1 foot
17.5 (5.3)
+45
-45
7
8.5
+45
-30
5.5
6
* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).