Fm approval and performance report – continued – Det-Tronics X3302 Multispectrum IR Flame Detector User Manual
Page 30
28
95-8576
9.2
0°
15°
45°
15°
30°
30°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
0°
15°
30°
45°
15°
30°
45°
50 (15.2)
45 (13.7)
40 (12.2)
35 (10.7)
30 (9.1)
25 (7.6)
20 (6.1)
15 (4.6)
10 (3)
5 (1.5)
5 (1.5)
10 (3)
15 (4.6)
20 (6.1)
25 (7.6)
30 (9.1)
35 (10.7)
40 (12.2)
45 (13.7)
50 (15.2)
Field of View at Indicated Distance in Feet (m) for
hydrogen at
Medium Sensitivity (30 inch plume, with 100 SLPM flow rate)
0°
15°
15°
30°
45°
30°
45°
35 (10.7)
30 (9.1)
25 (7.6)
20 (6.1)
15 (4.6)
10 (3)
5 (1.5)
5 (1.5)
10 (3)
15 (4.6)
20 (6.1)
25 (7.6)
30 (9.1)
35 (10.7)
0°
15°
45°
15°
30°
30°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
Field of View at Indicated Distance in Feet (m) for
Methanol at Medium Sensitivity (1 x 1 ft)
0°
15°
15°
30°
45°
30°
45°
17.5 (5.3)
15 (4.6)
10 (3)
5 (1.5)
5 (1.5)
10 (3)
15 (4.6)
17.5 (5.3)
0
°
15
°
45
°
15
°
30
°
30
°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
FM Approval and performance Report – Continued
0°
15°
30°
45°
15°
30°
45°
0°
15°
45°
15°
30°
30°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
25 (7.6)
20 (6.1)
15 (4.6)
10 (3)
5 (1.5)
5 (1.5)
10 (3)
15 (4.6)
20 (6.1)
25 (7.6)
Field of View at Indicated Distance in Feet for
hydrogen at
Low Sensitivity (30 inch plume, with 100 SLPM flow rate)
NOTE
FM Approvals minimum requirements are response distance measurements at 0° (on axis) and the limits of
the field of view. These high resolution field of view diagrams show the measured response distances at all the
indicated angles in the horizontal plane.
Field of View at Indicated Distance in Feet for
Methanol at Low Sensitivity (1 x 1 ft)