APPENDIX D

IECEx aPPROVaL

PointWatch Detector Model PIR

9400

IECEx ULD

10.0017

X

Ex d IIB+H

2

T

4

-T

6

Gb

T

6

(Tamb = –55°C to +50°C)

T

5

(Tamb = –55°C to +60°C)

T

4

(Tamb = –55°C to +75°C)

IP

66

.

IEC Standards: IEC

60079-0: 2007

IEC

60079-1: 2007

IEC

60529, 2.1

.ed.+Corr.

1:2003+2:2007

.

CONDITIONS OF CERTIFICATION:
The PointWatch, Model PIR

9400

Infrared Hydrocarbon Gas Detector has a threaded wire feed through incorporating

flying leads. This feed through is to be screwed into the cable entry opening of a suitable certified (Ex ‘d’ or Ex ‘e’)

enclosure in which the flying leads are to be terminated.

In order to maintain the Ingress Protection rating IP

66

, the back end of the PointWatch, Model PIR

9400

Infrared

Hydrocarbon Gas Detector with the flying lead is to be screwed into a suitable IECEx certified (Ex ‘d’ or Ex ‘e’) enclosure

with an Ingress Protection rating of at least IP

66

.

The captive front end screws are to be tightened with

1

N·m.

PointWatch Termination Box Model PIRTB

IECEx ULD

10.0002

Ex d

II

C T

5

-T

6

Gb

T

6

(Tamb = –55°C to +

60°

C)

T

5

(Tamb = –

55°

C to +

75°

C)

IP

66

.

IEC Standards: IEC

60079-0: 2007

IEC

60079-1: 2007

IEC

60529, 2.1

.ed.+Corr.

1:2003+2:2007.

All cable entry devices and blanking elements shall be certified in type of explosion protection flameproof enclosure

‘d’, suitable for the conditions of use and correctly installed. Unused apertures shall be closed with suitable certified

blanking elements.

For ambient temperatures below –

10°

C and above +

60°

C, use field wiring suitable for both minimum and maximum

ambient temperatures.