Det-Tronics GP16XX Standard Gas Panel User Manual
Page 5
![background image](/manuals/557579/5/background.png)
1.1
95-8671
3
system components
The system has three (3) main component groups – the
System Controller, LON, and 4-20 mA field devices. The
following devices are included (or optional) with the
GP16XX Gas Panel.
EQ3001 – EQP Controller (included)
The EQP Controller is the first and most critical component
of the GP16XX Gas Panel. With pre-programmed logic
from Det-Tronics' Safety System Software (S
3
), the
controller performs all communication, command, and
control functions for the system.
EQ3710AIM – Analog Input Module (optional up to 2)
The 8 channel Analog Input Module allows a device with
a calibrated 4-20 mA output signal to be connected to the
Eagle Quantum Premier Controller.
EQ2220GFM – Ground Fault Monitor (included)
The EQ2220GFM detects ground fault conditions on +/-
power and all secondary I/O circuits.
Power Supply – 24 Vdc, 10A (included)
The Power Supply provides main power to the EQP
Controller. It includes features such as voltage regulation,
high efficiency, and high power factor.
Pro-face Human Interface Machine (HMI) – (included)
The HMI touch screen consists of several graphical
screens that permit the setup, operation, and
interrogation of the connected field devices. See the
Operator Interface section for detailed descriptions of
the HMI touch screen.
FIElD DEVICES
The following field devices are GP16XX compatible:
PIRECl – PointWatch Eclipse
®
The PointWatch Eclipse Model PIRECL is a diffusion-
based, point-type infrared gas detector that provides
continuous monitoring of combustible hydrocarbon gas
concentrations in the range of 0 to 100% LFL. When
used with the GP16XX, the PIRECL can be setup through
the AIM or LON, depending on the model type.
UD10-DCU – FlexVu Universal Display
The FlexVu Model UD10-DCU is designed for applications
that require a gas detector with digital readout of detected
gas levels. Its LON interface board makes the UD10-
DCU compatible with Eagle Quantum Premier systems
by digitizing the 4-20 mA analog signal from the attached
sensor/transmitter. The digitized value is then transmitted
as a process variable over the LON to the EQP controller.
The UD10-DCU can be used with various 4-20 mA gas
detection devices (with or without HART), including the
following Det-Tronics field devices:
• GT3000
• PIRECL
• PIR9400
• OPECL
• CGS
• NTMOS.
EQ22xxDCU/DCUEX – Digital Communication Unit
The EQ22xx series of digital communication units for
catalytic, combustible and toxic gas sensors digitizes the
analog signal and transmits the value to the controller.
4-20 mA Devices
Connect 4-20 mA devices to the GP16XX via:
• AIM
• UD10-DCU
• EQ22xxDCU/DCUEX.
Reference Table 1 for the documentation list that contains
device specific information on approvals, installation,
calibration, and maintenance.
TITlE
FORM NUMBER
EQP Controller
95-8533
AIM
95-8533/90-1183
EQ22xxDCU
95-8533/90-1118
UD10-DCU
95-8656
ECLIPSE
95-8526
Table 1—EQP Device Specific Documentation