Setup – Det-Tronics GP16XX Standard Gas Panel User Manual
Page 11
1.1
95-8671
9
setup
The GP16XX can be setup in one of three ways:
1. An EQP only configuration, allowing all 16 channels
to be used for LON devices.
2. One AIM mounted inside the enclosure that powers 8
individual 4-20 mA devices, with the other 8 channels
used for LON devices.
3. Two AIMs mounted inside the enclosure to power 16
individual 4-20 mA devices.
NOTE
Analog Input Modules are pre-installed with
resistors from the factory. At minimum, one channel
(for each AIM)
must remain active, otherwise a
fault will be generated.
DEFAUlT SETUP SETTINGS
If the GP16XX Gas Panel is ordered without specifying
factory settings in the Configuration Worksheet, the
following default settings will be assumed:
–
Range: 0-100
–
Low Alarm: 20
–
High Alarm: 40
Note: unit of measure is percent of scale.
4-20 mA DEVICE SETUP
NOTE
The following setup instruction assumes that
all wiring from the device to the AIM has been
completed and the GP16XX is powered up.
Reference the device specific instruction manual
for wiring and calibration information.
The following example is for a GT3000 gas detector
connected to a Sensor Termination Box model STB, for
use with an AIM:
1. Power up the GT3000 and allow it to reach the
normal operating mode. Refer to the GT3000
manual, 95-8616, for startup procedures.
2. From the Main screen press the SETUP button.
3. The Setup screen will open. Touch an empty channel
to open the Setup Login screen (Figure 7).
NOTE
The user ID and password will be required every
time setup is initiated from the Main screen.
4. Touch the "User ID" input field to open the User
ID Input screen (Figure 10). Using the on-screen
keyboard, type "ADMIN" then press the ENT (Enter)
button to accept the user ID.
5. The Setup Login screen will re-open. Touch the
"Password" input field to open the Password Input
screen (Figure 10). Using the on-screen keyboard,
type "DEC" and press ENT to accept the password.
6. The Setup Login screen will re-open. Press the OK
button to accept the user ID and password.
7. The Device Setup screen will open. Touch the
Custom Device ID field to activate the cursor. Type
an 8 character limit tagname for the GT3000, and
make sure to press the ENT button to submit the
tagname
.
ImpoRtANt
The tagname will not be accepted unless the ENT
button is pressed.
8. Still in the Device Setup screen, select AIM as the
device type and press the SAVE button. The Setup
screen will open, showing the activated channel.
9. Calibrate the device using information in the device
specific instruction manual.
NOTE
Calibration of 4-20 mA devices cannot be initiated
or monitored from the GP16XX, only locally on the
4-20 mA device.
Figure 10—user ID and Password Input Screen(s)
CAPS LOCK*
ESCAPE
(Return to Device
Setup Login screen)
CLEAR
(Clears the text field)
BACKSPACE
(Delete one character
at a time)
USER ID/PASSWORD
INPUT FIELD
*NOTE
IN THE USER ID AND PASSWORD INPUT SCREENS, THE CAPS LOCK IS ACTIVATED BY
DEFAULT AND MUST REMAIN ACTIVATED WHEN ENTERING THE USER ID AND PASSWORD.
BOTH THE USER ID AND PASSWORD ARE CASE SENSITIVE.