Start up, Electrical connections – Clarus Environmental Fusion Series Treatment Systems 2800/3200/3600/4000 User Manual
Page 10
10
© Copyright 2013. All rights reserved.
Table 5 - Backwash Flow Rate Setting
Model
ZFL2800
ZFL3200
ZFL3600
ZFL4000
Backwash flow rate
(sec/liter)
50-70
54-75
58-81
63-89
Valve open (%)
60-70%
65-75%
60-70%
60-70%
Figure 15 - Flow Controlling Valve
Figure 14 - Flow Measurement
Model
ZFL2800
ZFL3200
ZFL3600 ZFL4000
Recirculating flow rate
(liter/min.)
9.7-15
11-17
13-19
14-21
Suggested Valve Opening
60-65%
55-60%
55-60%
50-55%
Table 4 - Recirculation Flow Rates
DOTTED
SCALE
VALVES
SUGGESTED
RANGE
MARKER
CONTAINER
RECIRCULATION OR
BACKWASH PIPE
1. Connect house sewer pipe or septic tank outlet, if required, to the
unit inlet. Make certain only household waste enters the unit (no
foundation drains, gutter drains, etc.).
2. Connect the outlet pipe to the outlet of the unit.
PIPING INSTALLATION
HIGH WATER ALARM FLOAT INSTALLATION
The Fusion
®
alarm panel assembly includes a high water alarm float
switch that is used to monitor the liquid level in the Fusion unit. The
switch should be tethered to one of the gray, vertical air lines in the
aeration chamber. With a 3" (76 mm) tether length, the cord should
pass through the opening in the partition wall between the aeration
and anaerobic chamber, and allow the float to hang in the outlet baffle
of the anaerobic chamber.
1. The float switch should be tethered to one of the gray, vertical pipes in
the aeration chamber. When the float is in the horizontal position,
the cord should be at least 1" (25 mm) below the top of the
partition wall opening in the anaerobic chamber baffle.
2. Place the cord into the clamp and secure to gray aeration pipe.
NOTE: Do not install the cord under the hose clamp.
3. Position the float with a 3" (76 mm) tether.
4. Tighten the hose clamp with a screwdriver. Be careful not to
overtighten as this may cause damage to the plastic clamp.
5. Make sure the float cord is not allowed to touch the excess hose
clamp band during operation as this may cause damage to the cord.
1.
All electrical installations must follow the
National Electrical Code and/or your local/state electrical codes.
2. The blower should be directly wired into the alarm panel. The
alarm panel must be located in a dry location that is accessible
for maintenance. Please see the wiring diagram and instructions
enclosed with the alarm panel.
3. Make certain the timer within the control panel is set to the proper
time. The timer unit display should be set to 10 hours and the
timer dial needle set to 3.6 for 36 hours. This will activate an
alarm if the blower doesn't go into backwash cycle within a 36-
hour time frame.
ELECTRICAL CONNECTIONS
There are two aeration systems provided within the aeration
chamber; normal aeration and backwash. Normally valves (1 and 3)
are set at 50%. Observe the air flow on each side of the unit to verify
equal flow. If there is an obvious discrepancy in air flow between the
two sides, adjust the valves (1 and 3) so that the flow is equal.
Figure 13 - Aeration Flow Adjustment
START UP
An installation and start-up check list is furnished
with the information package in the blower box. Please use this as a
guide and fill out all sections and return to your distributor.
Valve legend:
1. Aeration
Blue
Balance Aeration
2. Recirculation
Gray
See Table 2
3. Backwash
Red
Balance Backwash
4. Sludge transfer Gray
See Table 3
6. The float switch cord should be installed in electrical conduit
connecting the control panel to the Fusion
®
unit. The electrical
conduit must be rated for burial.
7. A ½" (13 mm) bulkhead fitting (supplied by others) should be used
to connect the electrical conduit to the Fusion
®
unit. A hole must be
drilled through the wall of the Fusion
®
unit between the red and blue
bulkhead fittings to facilitate this connection.
8. Please be certain that the bulkhead fitting for the electrical
conduit forms a watertight connection with the FRP wall of the
Fusion
®
unit. Silicone may be used to create a watertight seal.
9. Electrical conduit from the Fusion
®
unit to the alarm panel can be
buried in the same trench as the air lines.
10. The high-water alarm float switch is wired directly into the alarm
panel.