Code Description

Recommended

Troubleshooting of Lockout Codes

Code

1. Check wiring and correct any potential wiring errors.
2. Check High Fire Switch to assure proper function (not welded
or jumpered).
3.Manually drive the motor to the High Fire position and adjust
the HF switch while in this position and verify voltage through
the switch to the HFS input with a voltmeter.
4. If steps 1-3 are correct and the fault persists, replace the
module.

152 Combustion

pressure ON

H or L

153 Combustion

Pressure Off

OEM Specific
1. Check wiring and correct any errors.
2. Inspect the Combustion Pressure Switch to make sure it is
working correctly.
3. Reset and sequence the relay module.
4. During STANDBY and PREPURGE, measure the voltage
between J6 terminal 5 and L2 (N). Supply voltage should be
present. If not, the lockout switch is defective and needs
replacing.
5. If the fault persists, replace the relay module.

H or L

154 Purge

Fan

switch

On

H or L

155 Purge

fan

switch

OFF

OEM Specific
1. Purge fan switch is on when it should be off.
2. Check wiring and correct any errors.
3. Inspect the Purge Fan switch J6 terminal 3 and its
connections. Make sure the switch is working correctly and is
not jumpered or welded.
4. Reset and sequence the relay module.
5. If the fault persists, replace the relay module.

H or L

156 Combustion

pressure and
Flame ON

H or L

157 Combustion

pressure and
Flame OFF

OEM Specific
1. Check that flame is not present in the combustion chamber.
Correct any errors.
2. Make sure that the flame detector is wired to the correct
terminal.
3. Make sure the F & G wires are protected from stray noise
pickup.
4. Reset and sequence the module, if code reappears, replace
the flame detector.
5. Reset and sequence the module, if code reappears, replace
the module.

L

158

Main valve ON

L

159

Main valve OFF

OEM Specific
1. Check Main Valve terminal wiring and correct any errors.
2. Reset and sequence the module. If fault persist, replace the
module.

L

160 Ignition

ON

L

161 Ignition

OFF

OEM Specific
1. Check Ignition terminal wiring and correct any errors.
2. Reset and sequence the module. If fault persist, replace the
module.

L

162

Pilot valve ON

L

163

Pilot valve OFF

OEM Specific
1. Check Pilot Valve terminal wiring and correct any errors.
2. Reset and sequence the module. If fault persist, replace the
module.

L

164

Block intake ON

OEM Specific

L