beautypg.com

Bryan Boilers Triple-Flex High Efficiency Boilers & 300 User Manual

Page 39

background image

Date:

8-4-2010

Revision: 0

Form:

2396

33

323

Abnormal Recycle: Safety Relay off
after 10 seconds of RUN

324

Abnormal Recycle: Hardware flame
bias

325

Abnormal Recycle: Hardware static
flame

326

Abnormal Recycle: Hardware flame
current invalid

327

Abnormal Recycle: Hardware flame
rod short

328

Abnormal Recycle: Hardware invalid
power

329

Abnormal Recycle: Hardware invalid
AC line

330

Abnormal Recycle: Hardware SLO
flame ripple

331

Abnormal Recycle: Hardware SLO
flame sample

332

Abnormal Recycle: Hardware SLO
flame bias range

333

Abnormal Recycle: Hardware SLO
flame bias heat

334

Abnormal Recycle: Hardware SLO
spark stuck

335

Abnormal Recycle: Hardware SLO
spark changed

336

Abnormal Recycle: Hardware SLO
static flame

337

Abnormal Recycle: Hardware SLO
rod shorted

338

Abnormal Recycle: Hardware SLO
AD linearity

339

Abnormal Recycle: Hardware SLO
bias not set

340

Abnormal Recycle: Hardware SLO
bias shorted

341

Abnormal Recycle: Hardware SLO
electronics

342

Abnormal Recycle: Hardware
processor clock

343

Abnormal Recycle: Hardware AC
phase

344

Abnormal Recycle: Hardware A2D
mismatch

345

Abnormal Recycle: Hardware VSNSR
A2D

346

Abnormal Recycle: Hardware 28V
A2D

347

Abnormal Recycle: Hardware HFS
IAS shorted

348

Abnormal Recycle: Hardware PII
INTLK shorted

349

Abnormal Recycle: Hardware HFS
LCI shorted

350

Abnormal Recycle: Hardware HFS
LFS shorted

351

Abnormal Recycle: Invalid zero
crossing

352 Abnormal

Recycle:

fault stack sensor

353

Abnormal Recycle: stack limit

354

Abnormal Recycle: delta T limit

355

Abnormal Recycle: fault outlet sensor

356

Abnormal Recycle: outlet high limit

357

Abnormal Recycle: fault DHW sensor

358

Abnormal Recycle: DHW high limit

359

Abnormal Recycle: fault inlet sensor

360

Abnormal Recycle: Check
Parameters Failed

361

Internal error: No factory parameters
were detected in control

362

Internal error: PID iteration frequency
was invalid

363

Internal error: Demand-Rate interval
time was invalid

364

Internal error: Factory calibration
parameter for modulation was invalid

365

Internal error: CH PID P-scaler was
invalid

366

Internal error: CH PID I-scaler was
invalid

367

Internal error: CH PID D-scaler was
invalid

368

Internal error: DHW PID P-scaler was
invalid

369

Internal error: DHW PID I-scaler was
invalid

370

Internal error: DHW PID D-scaler was
invalid

371

Internal error: Lead Lag master PID
P-scaler was invalid

372

Internal error: Lead Lag master PID I-
scaler was invalid

373

Internal error: Lead Lag master PID
D-scaler was invalid

374-
459

RESERVED

460

LCI demand lost in run

461

Demand lost in run

462

STAT demand lost in run

463

Demand lost in run due to no flame

464-
466

RESERVED

467

Internal error: EEPROM write was
attempted before EEPROM was
initialized

468

Internal error: EEPROM cycle count
address was invalid