53

Illegal Modbus read was attempted

54

Safety processor brown-out reset
occurred

55

Application processor watchdog reset
occurred

56

Application processor brown-out reset
occurred

57

Safety processor watchdog reset
occurred

58

Alarm was reset by the user at the
control

59

Burner control firing rate was >
absolute max rate

60

Burner control firing rate was <
absolute min rate

61

Burner control firing rate was invalid,
% vs. RPM

62

Burner control was firing with no fan
request

63

Burner control rate (nonfiring) was >
absolute max rate

64

Burner control rate (nonfiring) was <
absolute min rate

65

Burner control rate (nonfiring) was
absent

66

Burner control rate (nonfiring) was
invalid, % vs. RPM

67

Fan off cycle rate was invalid, % vs.
RPM

68

Setpoint was overridden due to
sensor fault

69

Modulation was overridden due to
sensor fault

70-74 RESERVED

75

Absolute max fan speed was out of
range

76

Absolute min fan speed was out of
range

77

Fan gain down was invalid

78

Fan gain up was invalid

79

Fan minimum duty cycle was invalid

80

Fan pulses per revolution was invalid

81

Fan PWM frequency was invalid

82-89 RESERVED
90

Modulation output type was invalid

91

Firing rate control parameter was
invalid

92

Forced rate was out of range vs.
min/max modulation

93

Forced rate was invalid, % vs. RPM

94

Slow start ramp value was invalid

95

Slow start degrees value was invalid

96

Slow start was ended due to outlet
sensor fault

97

Slow start was end due to reference
setpoint fault

98

CH max modulation rate was invalid,
% vs. RPM

99

CH max modulation rate was >
absolute max rate

100

CH modulation range (max minus
min) was too small (< 4% or 40 RPM)

101

DHW max modulation rate was
invalid, % vs. RPM

102

DHW max modulation rate was >
absolute max rate

103

DHW modulation range (max minus
min) was too small (< 4% or 40 RPM)

104

Min modulation rate was < absolute
min rate

105

Min modulation rate was invalid, %
vs. RPM

106

Manual rate was invalid, % vs. RPM

107

Slow start enabled, but forced rate
was invalid

108

Analog output hysteresis was invalid

109

Analog modulation output type was
invalid

110

IAS open rate differential was invalid

111

IAS open step rate was invalid

112-
114

RESERVED

115

Fan was limited to its minimum duty
cycle

116

Manual rate was > CH max
modulation rate

117

Manual rate was > DHW max
modulation rate

118

Manual rate was < min modulation
rate

119

Manual rate in Standby was >
absolute max rate

120

Modulation commanded rate was >
CH max modulation rate

121

Modulation commanded rate was >
DHW max modulation rate

122

Modulation commanded rate was <
min modulation rate

123

Modulation rate was limited due to
outlet limit

124

Modulation rate was limited due to
Delta-T limit

125

Modulation rate was limited due to
stack limit

126

Modulation rate was limited due to
anti- condensation

127

Fan Speed out of range in RUN

128

Modulation rate was limited due to
IAS was open