Gas
Manifold
Pressure
(IWC)

4.4 3.6 4.0 2.0

Max RPM

6000-
7000

5100-
5500

3550-
4200

2700-
2850

Low Fire
Gas
Manifold
Pressure
(IWC)

.3 .3 .2 .2

Min RPM

1200-
1600

1200-
1600

800-
950

800-
950

Table 9 Approximate Boiler Settings

2.3.9 G

AS

M

ETER

R

EADINGS

Burner input rate can be checked by taking
readings from the gas meter. Please note
checking the rate with a meter is the only way to
be sure of input. Manifold readings are only an
approximate value and may vary from unit to
unit.

In order to obtain accurate data, there must be
no other appliances using gas from the same
meter while the burner input rate is being
checked.

A stopwatch or a watch with a second hand is
required to obtain a meter reading. Clock the
amount of time it takes for the smallest dial to
complete one revolution in seconds. Use the
following formula to obtain the cubic feet per
hour throughput of the unit.

seconds

in

time

g

clocked

V

gas

of

3600

c

c

1

3

=

=

=

=

ft

hr

ft

CFH

g

V

CFH

c

c


To obtain the Btu per hour throughput of the unit
use the following formula.

( )

3

-

ft

Btu

in

fuel

of

value

heating

=

=

v

v

h

h

CFH

Q


If the meter is not calibrated for gas temperature
and pressure, correction factors must be applied
to determine correct rate in SCFH (standard

cubic feet per hour). Consult the National Fuel
Gas Code (ANSI Z223.1, NFPA 54) or the local
gas utility for further information. Refer to Table
10 for corre
ction factors for the gas pressure at
the meter. Refer to Table 11 for the gas
temperature correction factors.

Gas Pressure at Meter Corr. Factor
14" w.c.

1.034

21" w.c.

1.051

1 psig

1.061

2 psig

1.136

5 psig

1.340

Table 10 Gas Pressure Correction


Gas Temp. at Meter

Corr. Factor

40

°F

1.04

50

°F

1.02

60

°F

1.0

70

°F

.981

80

°F

.963

90

°F

.945

Table 11 Gas Temperature Correction


To correct for pressure and temperature use the
following formula.

2.2B

table

correction

re

temperatu

2.2A

table

correction

pressure

=

=

=

t

p

t

p

c

t

t

t

Qt

Q

38