RESERVED

272

Abnormal Recycle: Pressure sensor
fault

273

Abnormal Recycle: Safety relay drive
test failed

274

Abnormal Recycle: Demand off
during Pilot Flame Establishing
Period

275

Abnormal Recycle: LCI off during
Drive to Purge Rate

276

Abnormal Recycle: LCI off during
Measured Purge Time

277

Abnormal Recycle: LCI off during
Drive to Lightoff Rate

278

Abnormal Recycle: LCI off during
Pre-Ignition test

279

Abnormal Recycle: LCI off during
Pre-Ignition time

280

Abnormal Recycle: LCI off during
Main Flame Establishing Period

281

Abnormal Recycle: LCI off during
Ignition period

282

Abnormal Recycle: Demand off
during Drive to Purge Rate

283

Abnormal Recycle: Demand off
during Measured Purge Time

284

Abnormal Recycle: Demand off
during Drive to Lightoff Rate

285

Abnormal Recycle: Demand off
during Pre-Ignition test

286

Abnormal Recycle: Demand off
during Pre-Ignition time

287

Abnormal Recycle: Flame was on
during Safe Start check

288

Abnormal Recycle: Flame was on
during Drive to Purge Rate

289

Abnormal Recycle: Flame was on
during Measured Purge Time

290

Abnormal Recycle: Flame was on
during Drive to Lightoff Rate

291

Abnormal Recycle: Flame was not on
at end of Ignition period

292

Abnormal Recycle: Flame was lost
during Main Flame Establishing
Period

293

Abnormal Recycle: Flame was lost
early in Run

294

Abnormal Recycle: Flame was lost
during Run

295

Abnormal Recycle: Leakage test
failed

296

Abnormal Recycle: Interrupted air
flow switch was off during Drive to
Purge Rate

297

Abnormal Recycle: Interrupted air
flow switch was off during Measured
Purge Time

298

Abnormal Recycle: Interrupted air
flow switch was off during Drive to
Lightoff Rate

299

Abnormal Recycle: Interrupted air
flow switch was off during Pre-Ignition
test

300

Abnormal Recycle: Interrupted air
flow switch was off during Pre-Ignition
time

301

Abnormal Recycle: Interrupted air
flow switch was off during Main
Flame Establishing Period

302

Abnormal Recycle: Ignition failed due
to interrupted air flow switch was off

303

Abnormal Recycle: ILK off during
Drive to Purge Rate

304

Abnormal Recycle: ILK off during
Measured Purge Time

305

Abnormal Recycle: ILK off during
Drive to Lightoff Rate

306

Abnormal Recycle: ILK off during Pre-
Ignition test

307

Abnormal Recycle: ILK off during Pre-
Ignition time

308

Abnormal Recycle: ILK off during
Main Flame Establishing Period

309

Abnormal Recycle: ILK off during
Ignition period

310

Run was terminated due to ILK was
off

311

Run was terminated due to
interrupted air flow switch was off

312

Stuck reset switch

313

Run was terminated due to fan failure

314

Abnormal Recycle: Fan failed during
Drive to Purge Rate

315

Abnormal Recycle: Fan failed during
Measured Purge Time

316

Abnormal Recycle: Fan failed during
Drive to Lightoff Rate

317

Abnormal Recycle: Fan failed during
Pre-Ignition test

318

Abnormal Recycle: Fan failed during
Pre-Ignition time

319

Abnormal Recycle: Fan failed during
Ignition period

320

Abnormal Recycle: Fan failed during
Main Flame Establishing Period

321

Abnormal Recycle: Main Valve off
after 10 seconds of RUN

322

Abnormal Recycle: Pilot Valve off
after 10 seconds of RUN