2.2.21 C
ENTRAL
H
EAT
C
ONFIGURATION
► ► CONFIGURE
► CH - CENTRAL HEAT
CONFIGURATION
Figure 36 Central Heat Configuration (Central Heat Page)
CH enable
Disable or Enable Central
Heating Loop
Demand switch
Sensor for Central Heat
demand:
Sensor only
Sensor & STAT terminal
Sensor & Remote Stat
LCI & Sensor
Outdoor reset
Enabled
Disabled
CH has priority over Lead
Lag
Yes, No, Cancel
Figure 37 Central Heat Configuration (Setpoint Page)
Setpoint source
Local
S2 (J8-6) 4-20mA
Setpoint
Setpoint for normal
Central Heat modulation:
50 °F to 190 °F
Time of day setpoint
Setpoint when Time Of
Day switch is on. 50 °F to
190 °F
Off hysteresis
Differential above
setpoint when boiler is
turned off. 2 °F to 5 °F
On hysteresis
Differential from setpoint
when boiler is turned on.
2 °F to 30 °F
4 mA water temperature
50 °F to 190 °F
20 mA water temperature
50 °F to 190 °F
Figure 38 Central Heat Configuration (Modulation Page)
Modulation sensor
Outlet sensor, Inlet
sensor, S5 (J8-11)
Modulation Rate Source
Local
P-gain Gain
applied for the P portion
of the PID equation 0-400
I-gain Gain
applied for the I portion of
the PID equation 0-400
D-gain
Gain applied for the D
portion of the PID
equation 0-400
Hysteresis step time
(0=Disable hysteresis
stepping)
Time between hysteresis
step changes: 0-600
seconds
2.2.22 S
OUND
P
RESSURE
L
EVELS
Sound pressure levels were measured at 4-1/2’
above the floor and 3’ from the boiler at the
front, rear and two sides. See Table 6 for
decibel readings.
27
Decibel
Readings
Model Front Rear
Tube
Side
Right