2.2.21 C

ENTRAL

H

EAT

C

ONFIGURATION

► ► CONFIGURE

► CH - CENTRAL HEAT
CONFIGURATION

Figure 36 Central Heat Configuration (Central Heat Page)

CH enable

Disable or Enable Central
Heating Loop

Demand switch

Sensor for Central Heat
demand:

Sensor only
Sensor & STAT terminal
Sensor & Remote Stat
LCI & Sensor

Outdoor reset

Enabled
Disabled

CH has priority over Lead
Lag

Yes, No, Cancel


Figure 37 Central Heat Configuration (Setpoint Page)

Setpoint source

Local
S2 (J8-6) 4-20mA

Setpoint

Setpoint for normal
Central Heat modulation:
50 °F to 190 °F

Time of day setpoint

Setpoint when Time Of
Day switch is on. 50 °F to
190 °F

Off hysteresis

Differential above
setpoint when boiler is
turned off. 2 °F to 5 °F

On hysteresis

Differential from setpoint
when boiler is turned on.
2 °F to 30 °F

4 mA water temperature

50 °F to 190 °F

20 mA water temperature

50 °F to 190 °F

Figure 38 Central Heat Configuration (Modulation Page)

Modulation sensor

Outlet sensor, Inlet
sensor, S5 (J8-11)

Modulation Rate Source

Local

P-gain Gain

applied for the P portion
of the PID equation 0-400

I-gain Gain

applied for the I portion of
the PID equation 0-400

D-gain

Gain applied for the D
portion of the PID
equation 0-400

Hysteresis step time
(0=Disable hysteresis
stepping)

Time between hysteresis
step changes: 0-600
seconds

2.2.22 S

OUND

P

RESSURE

L

EVELS

Sound pressure levels were measured at 4-1/2’
above the floor and 3’ from the boiler at the
front, rear and two sides. See Table 6 for
decibel readings.

27

Decibel

Readings

Model Front Rear

Tube
Side

Right
Side