Code Description

Recommended

Troubleshooting of Lockout Codes

Code

2. Replace the stack sensor.
3. If previous steps are correct and fault persists, replace the
module

96 Outdoor sensor

fault

1. Check wiring and correct any possible errors.
2. Replace the outdoor sensor.
3. If previous steps are correct and fault persists, replace the
module.

H

97

Internal Fault: A2D
mismatch.

L

98 Internal Fault:

Exceeded VSNSR
voltage tolerance

L

99 Internal Fault:

Exceeded 28V
voltage tolerance

Internal Fault.
1. Reset Module.
2. If fault repeats, replace module.

L

100 Pressure Sensor

Fault

1. Verify the Pressure Sensor is a 4-20ma source.
2. Check wiring and correct any possible errors.
3. Test Pressure Sensor for correct operation.
4. Replace the Pressure sensor.
5. If previous steps are correct and fault persists, replace the
module.

H

101-
104

RESERVED

105

Flame detected out
of sequence

1. Check that flame is not present in the combustion chamber.
Correct any errors.
2. Make sure that the flame detector is wired to the correct
terminal.
3. Make sure the F & G wires are protected from stray noise
pickup.
4. Reset and sequence the module, if code reappears, replace
the flame detector.
5. Reset and sequence the module, if code reappears, replace
the module.

H or L

106

Flame lost in MFEP

L

107

Flame lost early in
run

L

108

Flame lost in run

L

109 Ignition

failed

1. Check pilot valve (Main Valve for DSI) wiring and operation -
correct any errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, flame detector, flame
detector setting or flame rod position.
5. If steps 1 through 4 are correct and the fault persists, replace
the module.

L

110 Ignition failure

occurred

H

111 Flame current

lower than WEAK
threshold

Hold time of recycle and hold option. Will not be a lockout fault.
Hold Only. Internal hardware test. Not a lockout.

H

112 Pilot test flame

timeout

Interrupted Pilot or DSI application and flame lost when system
in “test” mode.
1. Reset the module to restart.

L

113 Flame

circuit

timeout

Flame sensed during Initiate or off cycle, hold 240 seconds, if
present after 240 seconds, lockout.

L

114-
121

RESERVED