Tank level – Class1 Digital Display User Manual
Page 22
![background image](/manuals/546733/22/background.png)
22
Tank Level
Basic Calibration:
(2 point)
With the fluid tank empty, enter the
calibration password.
L L L R R R
The left (0%) bar will flash to indi-
cate that you are ready to calibrate
for an empty tank.
Activate the left switch followed by
the right switch.
The right (100%) bar will flash to
indicate that the display is ready to
calculate for a full tank.
When the tank is full, actuate the
right and then the left switch.
Calibration is complete.
If after checking the accuracy of
your calibration, you are not satis-
fied, you can perform the advanced
calibration procedure. This is rarely
necessary except in the case of
oddly shaped tanks.
Advanced Calibration: (5 point)
With the fluid tank empty, enter the
calibration password.
L L R R L L
The left (0%) bar will flash to indi-
cate that you are ready to calibrate
empty.
Activate the left switch followed by
the right switch.
The fifth bar from the left (25%) will
flash to indicate that the display is
ready to calculate for a quarter tank.
Fill the tank to 1/4 full, actuate the
right and then the left switch.
The tenth bar from the left (50%)
will flash to indicate that the display
is ready to calculate for a half tank.
Fill the tank to 1/2 full, actuate the
left and then the right switch.
The fifteenth bar from the left (75%)
will flash to indicate that the display
is ready to calculate for three fourths
tank.
Fill the tank 3/4 full, actuate the right
and then the left switch.
The right (100%) bar will flash to
indicate that the display is ready to
calculate for a full tank.
When the tank is full, actuate the
right and then the left switch.
Calibration is complete.