2000 Series | Program Entry Guide | 13.0

Relays

EN | 53

Bosch Security Systems | 7/05 | 35114F

13.0 Relays

A D133 or D134 Relay Module is required to use the
system’s external relay outputs (Terminals 9 and 10).
One module is required for each output used. Refer to
the Installation Manual for instructions.

You can program each of the system’s two relay
outputs with one or two functions. With the

Relay #

Logic

prompts, you can configure the outputs so they

activate when the condition for either function exists,
or only activate when the conditions for both functions
exist.

The D5200 Programmer displays an additional relay
parameter prompt if the Relay function you selected
requires you to program additional information.

For example, if you select the Follow Point function
for

Relay 1, Func 1

and press [Enter], the D5200

displays the parameter prompts,

Point 1

(Yes, No),

followed by

Point 2

(Yes, No), and so on until

Point

24

(Yes, No). The parameter prompts tell the system

what points the relay is to follow.

If you select Reset for

Relay 1, Func 1

and press

[Enter], the D5200 goes directly to

Relay 1, Func 2

.

The Reset function does not require any parameters.

13.1 Relay Function Logic

The

Relay 1

, and

Relay 2, Logic

prompts allow you

to further define the conditions under which the
control panel activates the relay drivers.

1 Relay 1 Logic

2 Relay 2 Logic

Default:

Function 1 Only

Selection: Function 1 Only

Function 1 or 2
Function 1 and 2

0

Function 1 Only

1

Function 1 or 2

2

Function 1 and 2

When

Relay 1 Logic

or

Relay 2 Logic

is set to

Function 1 Only, the system activates the relay output
when Function 1 calls for activation. Function 2 is
ignored.

When

Relay 1 Logic

or

Relay 2 Logic

is set to

Function 1 or 2, the system activates the relay output
when either Function 1 or Function 2 calls for
activation, or when both do.

When

Relay 1 Logic

or

Relay 2 Logic

is set to

Function 1 and 2, both Function 1 and Function 2
must call for activation before the system activates
the relay output.

13.2 Relay

Functions

3 Relay 1 Func 1

Default:

No Output

Selection: Refer to Table 18 (0 to 24)

The

Relay 1, Func 1

prompt sets Function 1 for

Relay Output 1 (Terminal 9).

4 Relay 1 Func 2

Default:

No Output

Selection: Refer to Table 18 (0 to 24)

The

Relay 1, Func 2

prompt sets Function 2 for

Relay Output 1 (Terminal 9).

5 Relay 2 Func 1

Default:

No Output

Selection: Refer to Table 18 (0 to 24)

The

Relay 2, Func 1

prompt sets Function 1 for

Relay Output 2 (Terminal 10).

6 Relay 2 Func 2

Default:

No Output

Selection: Refer to Table 18 (0 to 24)

The

Relay 2, Func 6

prompt sets Function 6 for

Relay Output 2 (Terminal 10)