2000 Series | Program Entry Guide | 8.0

Bell

EN | 29

Bosch Security Systems | 7/05 | 35114F

8.0 Bell

The prompts in this group configure the Alarm Output
(bell) at Terminals 4 and 5.

1 Bell Time

Default:

6

Selection: 0 to 255

The

Bell Time

prompt sets the minutes of alarm

output at terminals 4 and 5. Both Fire Bell function
(pulsed output) and the Burglary Bell function (steady
output) follow the

Bell Time

duration.

Enter the number of minutes of alarm output at
Terminals 4 and 5 for both Fire and Burglary (Non-
Fire) functions. If you are using the

Alarm on 2 Fail

feature, program at least 3 minutes in

Bell Time

.

Refer to below.

Check with your Authority Having
Jurisdiction (AHJ) to determine the
appropriate Bell Time for your installation.
Many communities restrict bell time.

2 Bell Time

Default:

No

Selection: Yes, No

0 No

1 Yes

If you set the

Bell Test

prompt to Yes, the system

sounds the bell for 2 seconds when users turn the
system All On by pressing the [9] key.

If the system sends Closing Reports, the bell sounds
when the receiver acknowledges the Closing Report. If
the system does not send Closing Reports, the bell
sounds at the expiration of Exit Delay.

3 Single Ring

Default:

No

Selection: Yes, No

0 No

1 Yes

Set the

Single Ring

prompt to Yes to limit the alarm

output from the same Non-Fire point to one per
arming cycle. Setting this prompt to No allows every
alarm activation from a Non-Fire point to generate an
alarm output during an arming cycle.

Fire points always provide alarm output for every
alarm activation.

Single Ring

only affects the

alarm output. It does not prevent reports from
being sent.

4 Alarm on 2 Fail

Default:

No

Selection: Yes, No

0 No

1 Yes

Setting the

Alarm on 2 Fail

prompt to Yes

provides an alarm output after two failed attempts
to transmit an Alarm Report from any point when
the system is on. Alarm output is provided even if
the point is not programmed for alarm output.

Bell Time

must be programmed with at least 3

minutes to use the

Alarm on 2 Fail

feature.

Set this prompt to No if you want to prevent an
alarm output from Silent points even when the
system fails to communicate with the receiver.

Refer to Section 11.0 Point Codes for information on
programming points for alarm output.