2000 Series | Program Entry Guide | 4.0

Receiver

EN | 15

Bosch Security Systems | 7/05 | 35114F

4.0 Receiver

4.1 Modem

Reports

1 Rcvr Format

Default:

Modem

Selection:

Modem, Pulse

0 Pulse

1 Modem

Set

Rcvr Format

to Modem to transmit reports in Modem II format with its advanced reporting capabilities.

You need firmware revision 8.00 or greater installed in your D6500 Receiver.

Table 2 shows the reports available.

The D6500 line card ack tone table must contain “Modem II for D9112.” Refer to the 6500: Line Program Entry
Guide
.

Set

Rcvr Format

to Pulse to transmit in 4x2 Pulse Format. Be sure to program codes for each report group. Refer

to the

Section

4.2

Pulse Report Groups.

Table 2: Modem II Reports Chart

Modem II Report

Description

AC FAILURE

No AC power to system. Control panel runs on battery.

AC RESTORE

AC Power is restored to normal.

ALARM REPORT POINT
001 (-099)

Alarm Report from Points 1 to 24 or from an A, B, C, key. Refer to Section 7.0 ABC Keys for
instructions on setting reports from the keys.

ALARM REPORT
RECENT CLOSING
ID=001
POINT=001(24)

If an alarm occurs within 2 minutes of a Closing event, the system sends an Alarm Recent
Close Report.

ALARM CROSS POINT
001 (-099)

Alarm Report from Points 1 to 24 with point code for Cross or Partner point.

The ALARM RECENT CLOSE message overrides the ALARM CROSS POINT message.

The ALARM EXIT ERROR message does not apply to Cross, Partner, Double Knock, or Alarm
Verification points

BATTERY LOW

System battery is low.

BATTERY MISSING

System battery is disconnected. Battery must be missing for 60 seconds.

BATTERY RESTORE

Missing or low battery is restored.

CANCEL REPORT

Cancel Report from keyswitch.

CANCEL REPORT ID
001 (-008)

Cancel Report with user ID for users 1 to 8.