2000 Series | Program Entry Guide | 9.0

Test Timer

EN | 31

Bosch Security Systems | 7/05 | 35114F

9.0 Test

Timer

The prompts in this group configure the system’s
automatic test report timer.

1 Test Interval

Default:

No Report

Selection: No Report, 1 Day, 7 Days, 28 Days

0 No

Report

1 1

Day

2 7

Days

3 28

Days

Set

Test Interval

to

No Report to disable the Test

Report feature.

Set

Test Interval

to

1 Day to transmit Test Reports

every 24 hours.

Set

Test Interval

to

7 Days to transmit Test Reports

every 7 days.

Set

Test Interval

to

28 Days to transmit Test Reports

every 28 days.

2 Hours to Next

Default:

0

Selection: 0 to 23

Enter the number of hours until the next Test Report
at this prompt.

The system adds the entries in the

Hours to Next

and

Minutes to Next

prompts and waits that period before

it sends the next Test Report to the receiver. From that
report on, the system sends reports at the interval set
by the

Test Intrvl

prompt.

If both the hours and minutes are 0 (zero), the system
sends the next report one interval from the end of
your programming session.

0101
0101
0101

If you use a remote programmer, the waiting
period begins after you complete the
programming session. If you did not send
program changes to the control panel
during the remote programming session you
must end the programming session with a
Reset Bye.

For D5200 Programmer or Keypad
programming, the waiting period begins
after you return the standby pin to normal
operation.

3 Minutes to Next

Default:

0

Selection: 0 to 59

Enter the number of minutes until the next Test
Report at this prompt.

The system adds the entries in the

Hours to Next

and

Minutes to Next

prompts and waits that

period before it sends the next Test Report to the
receiver. From that report on, the system sends
reports at the interval set by the

Test Intrvl

prompt.

If both the hours and minutes are 0 (zero), the
system sends the next report at the end of your
programming session.

0101
0101
0101

If you are using a remote programmer, the
waiting period begins after you complete
the programming session. You must end the
programming session with a Reset Bye.

For D5200 Programmer or Keypad
programming, the waiting period begins
after you return the standby pin to normal
operation.

4 Defer Test Rpt

Default:

No

Selection: Yes, No

0

No

1 Yes

Set the

Defer Test Rpt

prompt to Yes to defer the

Test Report one interval if another report is
transmitting in the current interval.