BRIGGSandSTRATTON.COM

Generator AC Connection System
Asingle-phase,three-wireACconnectionsystemisusedin

thehomegenerator.Thestatorassemblyconsistsofapair

ofstationarywindingswithtwoleadsbroughtoutofeach

winding.Thejunctionofleadsand33formstheneutral

lead.Keepfieldwiringtoaminimum.Acompleteschematic

andwiringdiagramcanbefoundlaterinthismanual.

NOTE:Neutralisnotbondedtogroundatgenerator.

Grounding the Generator
Groundthehomegeneratorperapplicablecodes,standards,

andregulations.ThegeneratorGNDlugislocatedinthe

controlpanelbox.

Utility Circuit Connection
“40VUtility”leadsmustberoutedinconduit.The

“40VUtility”leadsdeliverpowertothegenerator’scircuit

board,optionalbatterywarmerandoilwarmer.Thispower

alsochargesthebattery.Whenpowerontheseleadsislost,

thegeneratorwillstart.

Usingprovidedpoleconnectorplugandinstaller-supplied

minimum300V,14AWGcopperwire,connecteachcontrol

circuitterminalinthegeneratortothetwo-ampfuse

terminalsintheautomatictransferswitch.

Transfer Switch Communication
Using#18AWGtwistedpairconductors,nogreaterthan

00ftinlength,connectTxRxandTxRxGroundfromthe

generatorcontrolpaneltotheGNDandT/Ronthetransfer

switchcontrolboard.

Fault Detection System
Thegeneratormayhavetorunforlongperiodsoftimewith

nooperatorpresent.Forthatreason,thesystemisequipped

withsensorsthatautomaticallyshutdownthegenerator

intheeventofpotentiallydamagingconditions,suchas

lowoilpressure,hightemperature,overspeed,andother

conditions.RefertoFault Detection SysteminMaintenance

formoredetailedinformation.
TheownerwillusetheremoteLEDindicatortoobservethe

statusofthehomegeneratorsystem.Consultwiththeowner

foraconvenientlocation.Locatetheelectricalboxinan

areavisiblebythehomeownersuchasnearagaragedoor

openerorsecuritycontrolpanel.

To install the remote LED indicator:
1. PushtheLEDthroughthemountingplatefromthe

frontuntilitsnapsinplace.

IMPORTANT:TheLEDispolaritysensitive.
. Usingprovided10poleconnectorandinstaller-supplied

minimum18AWGwire,connecttheremoteLEDtothe

generatorcontrolboard+LEDandGNDconnection.

UsewirenutstoattachwiretoLEDleads.

3. Attachmountingplatetoinstaller-suppliedelectricalbox.

Generator

Transfer

Switch