Burnham ALP150 User Manual
Page 73

Table 25: Parameter Descriptions
Access
Code
Parameter
No.
Description
Factory Setting
ALP080
ALP105
ALP150
ALP210
ALP285
ALP399
no
access
Code
needed
1
T3set DHW
140
2
DHW system
1 (On)
3
CH system
1 (On)
4
T1top CH Mode
190
Access Code Required
5
T1foot CH Mode
130
6
T4 minimum
0
7
T4 maximum
60
8
T4 frost protection *
-22
9
T4 correction
0
10
Tblocking
32
11
Booster time
0
12
Tparallel shift
0
13/14
Maximum fanspeed CH
4450
4850
5500
6200
6300
5867
15/16
Maximum fanspeed DHW
4450
4850
5500
6200
6300
5867
17/18
Minimum fanspeed
1125
1250
1300
1375
1450
1267
19
Ignition fanspeed
3000
2300
20
CH postpump time
0
21
DHW postpump time
10.2
22
CH modulation hysteresis on
10
23
CH modulation hysteresis off
2
24
DHW modulation hysteresis on
10
25
DHW modulation hysteresis off
2
26
DHW detection hysteresis on
-8
27
DHW detection hysteresis off
10
28
CH blocking time
0
29
DHW blocking time
0
30
DHW-> CH blocking time
0
31
Modulate back difference T1-T2
54
32
RMCI Address
-1
33
Tplus: Setvalue addition for DHW
50
34-1
2nd CH-Circuit (1st digit)
0 (2nd Heating Circuit Off)
34-2
CH Type (2nd digit)
0 (Room Thermostat)
35-1
DHW 3=way valve or pump (1st digit)
1 (Hot Water Pump)
35-2
DHW-type (2nd digit)
3 (Storage Tank without NTC3)
36
Manual fanspeed
-1
37-1
PWM-pump level (1st digit)
4
37-2
PWM-pump level (2nd digit)
1
38
Tset hold boiler warm
36
39
Ttop for 2nd CH circuit
190
40
Tfoot for 2nd CH circuit
130
41
Thysteresis for 2nd CH circuit
10
42-1
Pump settings for CH and DHW
0 (CH Normal Pump)
42-2
Minimum Off Cycle (2nd digit)
0 (Not Active)
* Circulator will start when boiler supply sensor will detect temperature 44.6° F or less