beautypg.com

Caution – Burnham ALP150 User Manual

Page 26

background image

26

Figure 26: Cutting Vertical Terminal

a. Determine the centerline of the terminal location

on the roof. For flat roof, cut either 5-1/2”
diameter hole (80/125 mm concentric vent size)
or 6-1/2” diameter hole (100/150 mm concentric
vent size) for the terminal. For sloped roof, cut a
hole in the roof large enough for the terminal to
pass through the roof while remaining plumb.

CaUTiOn

if the boiler is located directly under the hole,
cover it while cutting the hole to prevent debris
from falling onto boiler.

b. Install the roof flashing using standard practice

on the roofing system of the structure.

c. If not already done, assemble the venting system

inside the building. The last section of pipe needs
to be on the same center line as the terminal
and within 19-1/4” of the top edge of the roof

flashing.

d. Measure distance “H” from the top edge of the

storm collar to the end of the last fitting as shown
in Figure 25.

e. Add 1” to distance “H”. Carefully mark this

length on the pipe as shown in Figure 26.

f. Cut the

outer pipe only at the point marked in

Step (e) using aviation shears, a hacksaw, or an

abrasive wheel cutter. Be careful to cut the pipe

square. De-burr the cut end with a file or emery
cloth.

g. Place a mark on the plastic inner pipe 3/8”

beyond the end of the outer pipe (Figure 26).

Use a fine tooth hacksaw to cut the plastic pipe

and be careful to cut the pipe square. De-burr the

cut edge of the plastic pipe with a file or emery
cloth.

h. Make a mark on the terminal section 1” from the

cut end of the outer pipe as shown in Figure 26.

i. Slip the terminal section through the roof from

the outside. Push into the last section of vent
pipe until the mark made in Step (h) is not
longer visible. Secure the terminal to the last
piece of pipe with three #10 x 1/2” sheet metal

screws. Drill a 1/8” hole through both outer
pipes to start these screws. Use a drill stop or
other means to ensure that the drill bit does
not penetrate more than 3/8” into the outer
pipe. Do not use a sheet metal screw longer

than 1/2”.

j. Secure the terminal section to the inside of

the roof structure using the mounting bracket
provided with the terminal (Figure 27).

Figure 25: Dimension "H"

This manual is related to the following products: