Table 2a: Rating Data - Models aLP080 thru aLP99 (0 to 2000 Feet Elevation above Sea Level)

Table 2B: Rating Data - Models aLP080 thru aLP99 (2001 to 000 Feet Elevation above Sea Level)

alpine Series gas-Fired Boilers

Model

Number *

Input

(MBH)

** Output

(MBH)

Net I=B=R

Ratings

Water (MBH)

AFUE

%

Thermal

Efficiency

(%)

Combustion

Efficiency (%)

Boiler Water

Volume

(Gal.)

Heat Transfer

Area (Sq. Ft.)

Min. Max.

ALP080

27

80

73

63

95

0.6

7.3

ALP105

35

105

96

83

95

0.7

9.1

ALP150

50

150

138

120

95

1.3

16.4

ALP210

70

210

194

169

95

1.7

21.8

ALP285

57

285

265

230

95

2.4

29.1

ALP399

80

399

377

328

94.1

94.5

3.4

41.8

*

Add Suffix “N” for Natural Gas or Suffix “P” for LP Gas Models.

notes:

** DOE Heating Capacity (ALP080 thru ALP285); Gross Output (ALP399)

Maximum Working Pressure, Water - 30 PSI Shipped from Factory (std.); 50 PSI - Optional

Maximum Allowable Temperature, Water - 210°F

Boilers are factory shipped as Natural Gas builds and have to be field adjusted for LP gas application. Refer to ‘System Start-

Up Section of this manual for detailed procedure.
For elevations above 2000 Feet, ratings should be reduced at the rate of four percent (4%) for each 1000 Feet above sea level.

alpine Series gas-Fired Boilers

* Model

Number

Input

(MBH)

** Output

(MBH)

Net I=B=R

Ratings

Water (MBH)

AFUE

%

Thermal

Efficiency

(%)

Combustion

Efficiency (%)

Boiler Water

Volume

(Gal.)

Heat Transfer

Area

(Sq. Ft.)

Min. Max.

ALP080

16

80

73

63

95

0.6

7.3

ALP105

21

105

96

83

95

0.7

9.1

ALP150

30

150

138

120

95

1.3

16.4

ALP210

42

210

194

169

95

1.7

21.8

ALP285

57

285

265

230

95

2.4

29.1

ALP399

80

399

377

328

94.1

94.5

3.4

41.8

*

Add Suffix “N” for Natural Gas or Suffix “P” for LP Gas Models.

notes:

** DOE Heating Capacity (ALP080 thru ALP285); Gross Output (ALP399)

Maximum Working Pressure, Water - 30 PSI Shipped from Factory (std.); 50 PSI - Optional (ALP080 thru ALP285)

Maximum Working Pressure, Water - 50 PSI Shipped from Factory (std.); (ALP399)

Maximum Allowable Temperature, Water - 210°F

Boilers are factory shipped as Natural Gas builds and have to be field adjusted for LP gas application. Refer to ‘System Start-

Up Section of this manual for detailed procedure.

Ratings shown are for installations at sea level and elevations up to 2000 Feet. For elevations above 2000 Feet, ratings should be

reduced at the rate of four percent (4%) for each 1000 Feet above sea level.