beautypg.com

Notice – Burnham ALP150 User Manual

Page 16

background image

16

7. Install Rodent Screen and Combustion Air Terminal

(supplied with boiler), see Figure 8 for appropriate

configuration.

8. Apply sealant between vent pipe and opening to

provide weather-tight seal

F.

CPVC/PVC Vertical Venting System

Refer to Figures 3, 4, 5, 8, 9 & 10.

nOTiCE

Roof penetrations require the use of roof flashing
and storm collar that are not supplied with boiler.

Vent Piping - Vertical

1. See Paragraph D for instructions on attaching the

vent system connector to the boiler.

2. Do not exceed maximum vent length. Refer to

Table 7 for pipe diameters and allowable lengths.

3. Horizontal vent pipe must maintain a minimum ¼

inch per foot slope down towards boiler.

4. Install fire stops where vent passes through floors,

ceilings or framed walls. The fire stop must close
the opening between the vent pipe and the structure.

5. Whenever possible, install vent straight through the

roof. Refer to Figures 9 and 10.

Figure 6 : Direct Vent - Side Wall Terminations

Figure : Location of Vent Terminal Relative to Windows, Doors, grades,

Overhangs, Meters and Forced air inlets (Combustion air Terminal not shown)

This manual is related to the following products: