Operating Instructions Temperature Indicating Controller CS4R
V1.2
•
05/2006
- 26 -
Attached functions
[Sensor correction]
[Setting value Lock]
[Indication and control range monitoring]
• If the input value exceeds the Indication range high limit value, the PV display blinks “
”, and
if the input value exceeds the Indication range low limit value, the PV display blinks “
”.
• If the input value exceeds the Control range, OUT is turned OFF (for DC current output type, OUT
low limit value).
However, for manual control, it outputs the preset manipulated variable.
Indication and Control ranges with Thermocouple and RTD inputs
Input Input
range
Indication range
Control range
–199.9 ... 400.0°C
–199.9 ... 450.0°C
–205.0 ... 450.0°C
K, T
–199.9 ... 750.0°F
–199.9 ... 850.0°F
–209.0 ... 850.0°F
–200 ... 1370°C
–250 ... 1420°C
–250 ... 1420°C
K
–320 ... 2500°F
–370 ... 2550°F
–370 ... 2550°F
–200 ... 1000°C
–250 ... 1050°C
–250 ... 1050°C
J
–320 ... 1800°F
–370 ... 1850°F
–370 ... 1850°F
0 ... 1760°C
–50 ... 1810°C
–50 ... 1810°C
R, S
0 ... 3200°F
–50 ... 3250°F
–50 ... 3250°F
0 ... 1820°C
–50 ... 1870°C
–50 ... 1870°C
B
0 ... 3300°F
–50 ... 3350°F
–50 ... 3350°F
–200 ... 800°C
–250 ... 850°C
–250 ... 850°C
E
–320 ... 1500°F
–370 ... 1550°F
–370 ... 1550°F
–200 ... 1300°C
–250 ... 1350°C
–250 ... 1350°C
N
–320 ... 2300°F
–370 ... 2350°F
–370 ... 2350°F
0 ... 1390°C
–50 ... 1440°C
–50 ... 1440°C
PL-
0 ... 2500°F
–50 ... 2550°F
–50 ... 2550°F
0 ... 2315°C
–50 ... 2365°C
–50 ... 2365°C
C(W/Re5-26)
0 ... 4200°F
–50 ... 4250°F
–50 ... 4250°F
–199.9 ... 850.0°C
–199.9 ... 900.0°C
–210.0 ... 900.0°C
–200 ... 850°C
–210 ... 900°C
–210 ... 900°C
–199.9 ... 999.9°F
–199.9 ... 999.9°F
–211.0 ... 1099.9°F
Pt100
–300 ... 1500°F
–318 ... 1600°F
–318 ... 1600°F
–199.9 ... 500.0°C
–199.9 ... 550.0°C
–206.0 ... 550.0°C
–200 ... 500°C
–206 ... 550°C
–206 ... 550°C
–199.9 ... 900.0°F
–199.9 ... 999.9°F
–211.0 ... 999.9°F
JPt100
–300 ... 900°F
–312 ... 1000°F
–312 ... 1000°F
Indication range with DC current and voltage inputs
[Scaling low limit value – Scaling span x 1%] … [Scaling high limit value + Scaling span x 10%]
However, if the input value exceeds the range –1999 … 9999, the PV display blinks “
”
or “
”.
Control range with DC current and voltage inputs
[Scaling low limit value – Scaling span x 1%] … [Scaling high limit value + Scaling span x 10%]
[Input burnout monitoring]
Input
Indication on the PV display at input burnout
Thermocouple blinks
[
]
RTD blinks
[
]
4 ... 20 mA DC
blinks [
]
0 ... 20 mA DC
scaled low limit setting
0 ... 1 V DC
blinks [
]
0 ... 5 V DC
scaled low limit setting
1 ... 5 V DC
blinks [
]
0 ... 10 V DC
scaled low limit setting