Operating Instructions Temperature Indicating Controller CS4R
V1.2
•
05/2006
- 19 -
7. Running
When mounting and wiring to the control panel (DIN rail) are finished, start the operation following the next
procedure.
(1) Turn the power supply to the CS4R series ON.
For approx. 3s after power on, character of the sensor type and temperature unit are indicated on the PV
display, and the input range high limit value is indicated on the SV display. See (Table 5-1).
(If any other value is set at the scaling high limit value setting, SV display indicates it.)
During this time, all outputs and LED indicators are in OFF status.
After that PV display indicates actual temperature and SV display indicates the main setting value.
(2) Input the setting value.
Input each setting value referring to “5. Setup”.
(3) Turn the load circuit power ON.
Starts control action so as to keep temperature of the controlled object at the main setting value.
8. Action explanations
8.1 OUT action
part : Acts ON or OFF.
Heating
(Reverse)
action
Cooling (Direct) action
Control
action
Cycle action is performed according to deviation
Control output
logic level
DC 0/12 V
Changes continuously according to deviation
Control output
analogue
current signal
(4...20 mA)
Indicator
(OUT) Green
Lit
Unlit
ON
OFF
SV setting
Proportional band
ON
OFF
0V DC
0/12V DC
12V DC
+
20mA DC
20 to 4mA DC
4 to 20mA DC
Proportional band
Lit
0V DC
12V DC
12/0V DC
20mA DC
4mA DC
Cycle action is performed according to deviation
Cycle action is performed according to deviation
Cycle action is performed according to deviation
Changes continuously according to deviation
+
+
+
+
+
+
+
+
+
+
+
Unlit
4mA DC
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
SV setting
Control output
relay