Operating Instructions Temperature Indicating Controller CS4R

V1.2

05/2006

- 24 -

Control output (OUT)

Relay contact

: Control capacity 3A 250V AC (Resistive load)

1A 250V AC (Inductive load COS ø =0.4)

Electrical life, 100,000 times

Logic level DC 0/12 V (non-contact voltage for SSR drive):

12

+ 2

- 0

V DC max. 40mA (Short circuit protected)

Analogue current signal : 4 … 20mA DC

Load resistance : max. 550

Ω

Output accuracy : Within ±0.3% of output span
Resolution :

12000

EVT output

Alarm output [Common output with Loop break alarm and Heater burnout alarm (option)]

The alarm action point is set by ± deviation to the main setting (excluding Process alarm) and when
input exceeds the range, alarm (EVT) is turned ON or OFF (High/Low limit range alarm).
When Deenergized is selected during the Energized/Deenergized selection, alarm (EVT) is activated
conversely.
Setting accuracy

: The same as indication accuracy

Action

: ON/OFF action

Hysteresis

: Thermocouple and RTD inputs : 0.1 … 100.0°C (°F)

DC voltage and current inputs : 1 … 1000 (The placement of the

decimal point follows the selection)

Output

: Open collector, Control capacity 24V DC 0.1A (Max.)

Alarm output action

: One alarm action is selectable from below by front key operation:

High limit, Low limit, High/Low limits, High/Low limit range, Process high,
Process low, High limit with standby, Low limit with standby,
High/Low limits with standby and No alarm action.

Energized/Deenergized : Alarm (EVT) output Energized/Deenergized can be selected.

Energized

Deenergized

Red (EVT) LED

Lights

Lights

EVT output

ON

OFF

Alarm HOLD function selection : Once the alarm is activated, alarm output is held until

the power is turned off.

Loop break alarm output (Common output with Alarm and Heater burnout alarm [Option])

Detects heater burnout, sensor burnout and actuator trouble.
Setting range:

time setting

: 0 … 200 minutes

span setting

: 0 … 150°C (°F) or 0.0 … 150.0°C (°F)

DC voltage and current inputs: 0 … 1500
(the placement of the decimal point follows the selection)

Output

: Open collector

control capacity 24V DC 0.1A (max.)

Converter function

: See “6. Converter function”