WIKA CS4R User Manual
Page 17
Operating Instructions Temperature Indicating Controller CS4R
V1.2
•
05/2006
- 17 -
Energized/Deenergized function
[If alarm action Energized is selected]
When the alarm output indicator is lit, the alarm output (between terminal 8 and 9) is conducted (ON).
When the alarm output indicator is unlit, the alarm output is not conducted (OFF).
[If alarm action Deenergized is selected]
When the alarm output indicator is lit, the alarm output (between terminal 8 and 9) is not conducted
(OFF).
When the alarm output indicator is unlit, the alarm output is conducted (ON).
High limit alarm (Energized setting) High limit alarm (Deenergized setting)
(Fig. 5.5-1) (Fig. 5.5-2)
5.6 Control output manipulated variable indication
Press the MODE key for approx. 3 seconds during PV/SV display mode.
Keep pressing the MODE key until the output manipulated variable shows up, though the main setting
mode appears during the process.
The control output manipulated variable is indicated on the SV display and the 1st
decimal point from the
right blinks in a 0.5 second cycle on the SV display.
Pressing the MODE key again, it reverts to the PV/SV display mode.
OFF
ON
A1 hysteresis
+ A1 set point
OFF
ON
+ A1 set point
A1 hysteresis