9. PID auto-tuning of the CS4R
In order to decide each P, I, D and ARW value automatically, this system gives a fluctuation to the controlled
object to get an optimal value. 1 of 3 types of fluctuation below is automatically selected.
[When the difference between the setting value and processing temperature is large as the
temperature rises]
When AT bias is set to 20°C (°F), fluctuation is applied at the temperature 20°C (°F) lower than the setting
value.
Temperature 20°C (°F) lower than the setting value
(1) Calculating PID constant
(2) PID constant calculated
(3) Controlled by the PID
constant set by auto-tuning.
(4) AT bias value
[When control is stable]
Fluctuation is applied at the setting value.
(1) Calculating PID constant
(2) PID constant calculated
(3) Controlled by the PID
constant set by auto-tuning
[When the difference between the setting value and processing temperature is large as the
temperature falls]
When AT bias is set to 20°C (°F), fluctuation is applied at the temperature 20°C (°F) higher than the setting
value.
Temperature 20°C (°F) higher than the setting value
(1) Calculating PID constant
(2) PID constant calculated
(3) Controlled by the PID
constant set by auto-tuning.
(4) AT bias value