Operating Instructions Temperature Indicating Controller CS4R

V1.2

05/2006

- 23 -

10. Specifications


10.1 Standard specification

Model name

: DIN rail mounting type indicating controller

Mounting method

: DIN rail mounting method

Setting

method

: Input system using membrane sheet key

Display

PV display

: Red LED 4 digits, character size 7.5 x 4.1 mm (H x W)

SV display

: Green LED 4 digits, character size 7.5 x 4.1 mm (H x W)

Input

Thermocouple : K, J, R, S, B, E, T, N, PL- , C (W/Re5-26)

External resistance: 100

Ω or less

However, for thermocouple B, external resistance, 40

Ω or less

RTD

: Pt100, JPt100, 3-wire system

Allowable input lead wire resistance: 10

Ω or less per wire

DC current

: 0 … 20mA DC, 4 … 20mA DC, input impedance 50

Ω

[Connect 50

Ω shunt resistor (sold optionally) between input terminals 5 and 6]

Allowable input current: 50mA or less

DC voltage

:

0 … 1V DC

0 … 5V / 1 … 5V / 0 … 10V DC

Input impedance

1M

Ω or greater 100kΩ or greater

Allowable input voltage 5V or less

15V or less

Allowable signal source
resistance

2k

Ω or less

100

Ω or less

Accuracy (Setting and Indication)

Thermocouple : Within ±0.2% of input span ±1 digit, or within ±2°C (4°F) whichever is greater

R, S inputs, 0 … 200°C (0 … 400°F): Within ±6°C (12°F)

B input, 0 … 300°C (0 … 600°F): Accuracy is not guaranteed.

K, J, E, T, N inputs, less than 0°C (32°F): Within ±0.4% of input span ±1 digit

RTD

: Within ±0.1% of input span ±1 digit, or within ±1°C (2°F) whichever is greater

DC voltage

: Within ±0.2% of input span ±1 digit

DC current

: Within ±0.2% of input span ±1 digit

Input sampling period

: 0.25 seconds

Control action

PID action (with auto-tuning function)

PI action

: When derivative time is set to 0

PD action (with manual reset function) : When integral time is set to 0

P action (with manual reset function) : When derivative and integral times are set to 0

ON/OFF action

: When proportional band is set to 0

Setting ranges of the control parameters :

OUT proportional band : 0.0 to 110.0% (ON/OFF action when set to 0.0)
Integral time

: 0 to 1000 seconds (Off when set to 0)

Derivative time

: 0 to 300 seconds (Off when set to 0)

OUT proportional cycle : 1 to 120 seconds
ARW

: 0 to 100%

Manual reset

: ± Proportional band converted value

Output limit

: 0 to 100% (DC current output type: –5 to 105%)

(Not available for ON/OFF action)

Hysteresis

: Thermocouple and RTD inputs: 0.1 to 100.0°C (°F)

DC voltage and current inputs: 1 to 1000

(The placement of the decimal point follows the selection)