beautypg.com

WIKA CS4R User Manual

Page 15

background image

Operating Instructions Temperature Indicating Controller CS4R

V1.2

05/2006

- 15 -

OUT high limit setting

Sets the OUT high limit value.

Not available for ON/OFF action.

Setting range: OUT low limit value to 105%

Setting greater than 100% is effective to DC
current output type.

100%

OUT low limit setting

Sets the OUT low limit value.

Not available for ON/OFF action.

Setting range: –5% to OUT high limit value

Setting less than 0% is effective to DC current
output type.

0%

OUT ON/OFF action hysteresis setting

Sets the ON/OFF action hysteresis for the OUT.

Available only for ON/OFF action (P=0).

Thermocouple and RTD inputs : 0.1 … 100.0°C (°F)

DC voltage and current inputs : 1 … 1000

(The placement of the decimal point follows the selection)

1.0°C

Alarm action selection

Selects an alarm action type.

No alarm action

:

High limit Alarm

:

Low limit alarm

:

High/Low limits Alarm

:

High/Low limit range Alarm

:

Process high Alarm

:

Process low Alarm

:

High limit alarm with standby

:

Low limit alarm with standby

:

High/Low limits alarm with standby :

No alarm action

Alarm action Energized/Deenergized

Selects the alarm action Energized/Deenergized.

Not available when “No alarm action” is selected in Alarm action

selection.

Energized :

Deenergized :

Energized

Alarm HOLD function selection

Selects whether alarm HOLD function is [Used] or not.

If alarm HOLD function is set to [Used], once the alarm
functions, alarm output remains until the power is turned off.

Not available when “No alarm action” is selected in Alarm

action selection.

Alarm HOLD [Not used] :

Alarm HOLD [Used]

:

Alarm HOLD
[Not used]

Alarm hysteresis setting

Sets the alarm hysteresis.

Not available when “No alarm action” is selected in Alarm action
selection.

Thermocouple and RTD inputs : 0.1 … 100.0°C (°F)
DC voltage and current inputs : 1 … 1000
(The placement of the decimal point follows the selection.)

1.0°C

Alarm action delayed timer setting

Sets the alarm action delayed time. The alarm is activated

when the setting time has passed after the input enters alarm
output range.

Not available when “No alarm action” is selected in Alarm action

selection.

0 seconds