WIKA CS4R User Manual
Page 15
Operating Instructions Temperature Indicating Controller CS4R
V1.2
•
05/2006
- 15 -
OUT high limit setting
•
Sets the OUT high limit value.
•
Not available for ON/OFF action.
•
Setting range: OUT low limit value to 105%
Setting greater than 100% is effective to DC
current output type.
100%
OUT low limit setting
•
Sets the OUT low limit value.
•
Not available for ON/OFF action.
•
Setting range: –5% to OUT high limit value
Setting less than 0% is effective to DC current
output type.
0%
OUT ON/OFF action hysteresis setting
•
Sets the ON/OFF action hysteresis for the OUT.
•
Available only for ON/OFF action (P=0).
•
Thermocouple and RTD inputs : 0.1 … 100.0°C (°F)
DC voltage and current inputs : 1 … 1000
(The placement of the decimal point follows the selection)
1.0°C
Alarm action selection
•
Selects an alarm action type.
No alarm action
:
High limit Alarm
:
Low limit alarm
:
High/Low limits Alarm
:
High/Low limit range Alarm
:
Process high Alarm
:
Process low Alarm
:
High limit alarm with standby
:
Low limit alarm with standby
:
High/Low limits alarm with standby :
No alarm action
Alarm action Energized/Deenergized
•
Selects the alarm action Energized/Deenergized.
•
Not available when “No alarm action” is selected in Alarm action
selection.
•
Energized :
Deenergized :
Energized
Alarm HOLD function selection
•
Selects whether alarm HOLD function is [Used] or not.
If alarm HOLD function is set to [Used], once the alarm
functions, alarm output remains until the power is turned off.
•
Not available when “No alarm action” is selected in Alarm
action selection.
•
Alarm HOLD [Not used] :
Alarm HOLD [Used]
:
Alarm HOLD
[Not used]
Alarm hysteresis setting
•
Sets the alarm hysteresis.
•
Not available when “No alarm action” is selected in Alarm action
selection.
•
Thermocouple and RTD inputs : 0.1 … 100.0°C (°F)
DC voltage and current inputs : 1 … 1000
(The placement of the decimal point follows the selection.)
1.0°C
Alarm action delayed timer setting
•
Sets the alarm action delayed time. The alarm is activated
when the setting time has passed after the input enters alarm
output range.
•
Not available when “No alarm action” is selected in Alarm action
selection.
0 seconds