beautypg.com

WIKA CS4R User Manual

Page 13

background image

Operating Instructions Temperature Indicating Controller CS4R

V1.2

05/2006

- 13 -

Sensor correction setting

Sets the sensor correction value of the sensor.

Thermocouple and RTD inputs : –100.0 … 100.0°C (°F)

DC voltage and current inputs : –1000 … 1000

(The placement of the decimal point follows the selection.)

0.0°C

Communication protocol selection

Selects communication protocol.

Available only when the option Digital interface [5] is added.

WIKA protocol

:

Modbus ASCII mode :

Modbus RTU mode

:

WIKA protocol

Instrument number setting

Sets an individual instrument number to each CS4R when
connecting plural CS4R in serial communication.

Available only when the option Digital interface [5] is added.

Setting range: 0 … 95

0

Data transfer rate selection

Selects a data transfer rate in accordance with host computer

Available only when the option Digital interface [5] is added.

2400bps :

4800bps :

9600bps :

19200bps :

9600bps

Parity selection

Selects the parity.

Not available when the option Digital interface [5] is not added

or when WIKA protocol is selected in Communication protocol
selection

None :

Even :

Odd :

Even

Stop bit selection

Selects the stop bit.

Not available when the option Digital interface [5] is not added

or when WIKA protocol is selected in Communication protocol
selection

Setting range: 1 or 2

1