Operating Instructions Temperature Indicating Controller CS4R

V1.2

05/2006

- 14 -

5.5 Auxiliary function setting mode 2

Character Name,

Description, Setting range

Default value

Input type selection

Selects a sensor type and temperature unit from thermocouple (10

types), RTD (2 types), DC current (2 types) and DC voltage (4
types).

When changing input type from DC voltage input to the others,

detach the sensor connected to this unit before changing.

Input circuit will break down if input type is changed while the

sensor is connected.

K

(

200 … 1370°C)

K

–200 ... 1370 °C:

–199.9 ... 400.0 °C:

J

–200 ... 1000 °C:

R

0 ... 1760 °C:

S

0 ... 1760 °C:

B

0 ... 1820 °C:

E

–200 ... 800 °C:

T

–199.9 ... 400.0°C:

N

–200 ... 1300 °C:

PL-

0 ... 1390 °C:

C (W/Re5-26)

0 ... 2315 °C:

Pt100

–199.9 ... 850.0 °C:

JPt100

–199.9 ... 500.0 °C:

Pt100

–200 ... 850 °C:

JPt100

–200 ... 500 °C:

4 ... 20mA DC –1999 ... 9999:

0 ... 20mA DC –1999 ... 9999:

0 ... 1V DC

–1999 ... 9999:

0 ... 5V DC

–1999 ... 9999:

1 ... 5V DC

–1999 ... 9999:

0 ... 10V DC –1999 ... 9999:

K

320 ... 2500 °F:

–199.9 ... 750.0 °F:

J

–320 ... 1800 °F:

R

0 ... 3200 °F:

S

0 ... 3200 °F:

B

0 ... 3300 °F:

E

–320 ... 1500 °F:

T

–199.9 ... 750.0 °F:

N

–320 ... 2300 °F:

PL-

0 ... 2500 °F:

C (W/Re5-26) 0 ... 4200 °F:

Pt100

–199.9 ... 999.9 °F:

JPt100

–199.9 ... 900.0 °F:

Pt100

–300 ... 1500 °F:

JPt100

–300 ... 900 °F:

note:
With the input configuration 4 ... 20 mA or
0 ... 20 mA a 50

Ω shunt resistor (sold

optionally) must be necessarily connected
between the terminals 5 and 6.

Scaling high limit setting

Sets the scaling high limit value.
The scaled high limit value is at the same time the maximal
adjustable set value.

Scaling low limit setting value to Input range high limit value

(For DC voltage and current inputs, the placement of the decimal
point follows the selection.)

1370°C

Scaling low limit setting

Sets the scaling low limit value.

The scaled low limit value is at the same time the minimal
adjustable set value.

Input range low limit value to scaling high limit setting value

(For DC voltage and current inputs, the placement of the decimal
point follows the selection.)

–200°C

Decimal point place selection

Selects the decimal point place.

However, not available if thermocouple or RTD input is selected
in the input type selection.

No decimal point

:

1 digit after decimal point :

2 digits after decimal point :

3 digits after decimal point :

No decimal
point

PV filter time constant setting

Sets the PV filter time constant.
If the setting value is too large, it affects control result due to the
response delay.

Setting range: 0.0 … 10.0 seconds

0.0 seconds