Operating Instructions Temperature Indicating Controller CS4H / CS4L
V1.1
•
05/2006
- 50 -
[Auxiliary function setting mode 1]
Character Setting
item
Default
value
Data
Setting value lock selection
Unlock
SV high limit setting
Input range high limit value
SV low limit setting
Input range low limit value
Sensor correction setting
0.0 °C
Communication protocol selection
WIKA protocol
Instrument number setting
0
Data transfer rate selection
9600 bps
Parity selection
Even
Stop bit selection
1
[Auxiliary function setting mode 2]
Character Setting
item
Default
value
Data
Sensor selection
K: –200 ... 1370 °C
Scaling high limit setting
9999
Scaling low limit setting
–1999
Decimal point place selection
No decimal point
PV filter time constant setting
0.0 seconds
OUT1 high limit setting
100 %
OUT1 low limit setting
0 %
OUT1 ON/OFF action hysteresis
1.0 °C
OUT2 action mode selection
Air cooling
OUT2 high limit setting
100 %
OUT2 low limit setting
0 %
Overlap band/Dead band setting
0.0 °C
OUT2 ON/OFF action hysteresis
1.0 °C
A1 action selection
No alarm action
A2 action selection
No alarm action
A1 action Energized/Deenergized
Energized
A2 action Energized/Deenergized
Energized
A1 hysteresis setting
1.0 °C
A2 hysteresis setting
1.0 °C
A1 action delayed timer setting
0 seconds
A2 action delayed timer setting
0 seconds
Direct (Cooling)/Reverse (Heating) action Reverse (Heating) action
AT bias setting
20 °C
SVTC bias setting
0
SV2 indication selection
Indication
Output status selection when input burn-
out
Output OFF
OUT/OFF key function selection
OUT/OFF function