WIKA CS4L User Manual
Page 26
Operating Instructions Temperature Indicating Controller CS4H / CS4L
V1.1
•
05/2006
- 26 -
Overlap band/Dead band setting [
]
• Sets Overlap band/Dead band for OUT1 and OUT2.
+ setting value: Dead band
– setting value: Overlap band
• Not available for ON/OFF action or when 2. control output (option) is not added
• Setting range: –100.0 … 100.0 °C (°F)
for DC input, 1 … 1000
(the placement of the decimal point follows the selection)
• Default: 0.0 °C
OUT2 ON/OFF action hysteresis setting [
]
• Sets ON/OFF hysteresis for OUT2.
• Available only when 2. control output (option) is added
• Setting range: 0.1 … 100.0°C (°F)
For DC input, 1 … 1000
(the placement of the decimal point follows the selection)
• Default: 1.0 °C
A1 action selection [
]
• Selects A1 action.
• Selection item:
No alarm action
:
Process high alarm
:
High limit alarm
:
Process low alarm
:
Low limit alarm
:
High limit alarm with standby
:
High/Low limits alarm
:
Low limit alarm with standby
:
High/Low limit range alarm :
High/Low limits alarm with standby :
• Default: No alarm action
A2 action selection [
]
• Selects A2 action.
• Available only when option [2AS] or [2AL] is added
• Selection item, default value are the same as those of A1 action selection.
A1 action Energized/Deenergized selection [
]
• Selects A1 action Energized/Deenergized.
• Not available when No alarm action is selected in the A1 action selection
• Selection item:
(Energized)
(Deenergized)
• Default: Energized
A2 action Energized/Deenergized selection [
]
• Selects Energized or Deenergized for A2 action.
• Not available when No alarm action is selected in the A2 action selection or when
option [2AS] or [2AL] is not added
• Selection item and default value are the same as those of A1 action Energized/
Deenergized selection.
A1 hysteresis setting [
]
• Sets A1 hysteresis.
• Not available when No alarm action is selected in the A1 action selection
• Setting range: 0.1 … 100.0 °C (°F)
For DC input, 1 … 1000
(the placement of the decimal point follows the selection)
• Default: 1.0 °C
A2 hysteresis setting [
]
• Sets A2 hysteresis.
• Not available when No alarm action is selected in the A2 action selection or when option [2AS] or
[2AL] is not added
• Setting range and default value are the same as those of A1 hysteresis setting.