beautypg.com

WIKA CS4L User Manual

Page 26

background image

Operating Instructions Temperature Indicating Controller CS4H / CS4L

V1.1

05/2006

- 26 -

Overlap band/Dead band setting [

]

• Sets Overlap band/Dead band for OUT1 and OUT2.

+ setting value: Dead band
– setting value: Overlap band

• Not available for ON/OFF action or when 2. control output (option) is not added
• Setting range: –100.0 … 100.0 °C (°F)

for DC input, 1 … 1000
(the placement of the decimal point follows the selection)

• Default: 0.0 °C
OUT2 ON/OFF action hysteresis setting [

]

• Sets ON/OFF hysteresis for OUT2.
• Available only when 2. control output (option) is added
• Setting range: 0.1 … 100.0°C (°F)

For DC input, 1 … 1000
(the placement of the decimal point follows the selection)

• Default: 1.0 °C
A1 action selection [

]

• Selects A1 action.
• Selection item:

No alarm action

:

Process high alarm

:

High limit alarm

:

Process low alarm

:

Low limit alarm

:

High limit alarm with standby

:

High/Low limits alarm

:

Low limit alarm with standby

:

High/Low limit range alarm :

High/Low limits alarm with standby :

• Default: No alarm action
A2 action selection [

]

• Selects A2 action.
• Available only when option [2AS] or [2AL] is added
• Selection item, default value are the same as those of A1 action selection.
A1 action Energized/Deenergized selection [

]

• Selects A1 action Energized/Deenergized.
• Not available when No alarm action is selected in the A1 action selection
• Selection item:

(Energized)

(Deenergized)

• Default: Energized
A2 action Energized/Deenergized selection [

]

• Selects Energized or Deenergized for A2 action.
• Not available when No alarm action is selected in the A2 action selection or when

option [2AS] or [2AL] is not added

• Selection item and default value are the same as those of A1 action Energized/

Deenergized selection.

A1 hysteresis setting [

]

• Sets A1 hysteresis.
• Not available when No alarm action is selected in the A1 action selection
• Setting range: 0.1 … 100.0 °C (°F)

For DC input, 1 … 1000
(the placement of the decimal point follows the selection)

• Default: 1.0 °C
A2 hysteresis setting [

]

• Sets A2 hysteresis.
• Not available when No alarm action is selected in the A2 action selection or when option [2AS] or

[2AL] is not added

• Setting range and default value are the same as those of A1 hysteresis setting.

This manual is related to the following products: