Operating Instructions Temperature Indicating Controller CS4H / CS4L

V1.1

05/2006

- 21 -

HB (Heater burnout alarm) setting [

and

X.X are indicated in turn.]

• Sets the heater current value for Heater burnout alarm.

Setting the value to 0.0 disables the function.

• Available only when Heater burnout alarm (option) is added
• When OUT1 is OFF, heater current value shows the same value as when OUT1 was on.

• It is recommended to set approx. 80 % of the heater current value (setting value) considering the

voltage fluctuation.

• Self-holding is not available for the alarm output.
• Setting range: Rating 5 A:

0.0 … 5.0 A

Rating 10 A: 0.0 … 10.0 A

Rating 20 A: 0.0 … 20.0 A

Rating 50 A: 0.0 … 50.0 A

• Default: 0.0 A
LA (Loop break alarm) action time setting [

]

• Sets the action time to assess the Loop break alarm.
• Available only when option [2AR] or [2AL] is added
• Setting range: 0 … 200 minutes
• Default: 0 minutes
LA (Loop break alarm) action span setting [

]

• Sets the action span to assess the Loop break alarm.
• Available only when option [2AS] or [2AL] is added
• Setting range: 0 … 150 °C (°F), however, with a decimal point 0.0 … 150.0 °C (°F)

For DC input, 0 … 1500 (The placement of the decimal point follows the selection.)

• Default: 0 °C

[A1, A2 setting range]

(Table 5.3-1)

Alarm action

Setting range

High limit alarm

–Input span to Input span °C (°F)

*1

Low limit alarm

–Input span to Input span °C (°F)

*1

High/Low limits alarm

0 to Input span °C (°F)

*1

High/Low limit range alarm

0 to Input span °C (°F)

*1

Process high alarm

Input range low limit to Input range high limit*2

Process low alarm

Input range low limit to Input range high limit*2

High limit alarm with standby

–Input span to Input span °C (°F)

*1

Low limit alarm with standby

–Input span to Input span °C (°F)

*1

High/Low limits alarm with standby

0 to Input span °C (°F)

*1


• When the input has a decimal point, the negative low limit value is –199.9, and the positive high limit

value is 999.9.

*1: For DC input, the Input span is the same as the Input range scaling span.

*2: For DC input, Input range low (high) limit value is the same as the Input range scaling low (high)

limit value.