Integral time setting [ ]
• Sets the integral time.

Setting the value to 0 disables the function. (PD action)

• Not available when OUT1 is ON/OFF action
• Setting range: 0 … 1000 seconds
• Default: 200 seconds
Derivative time setting [ ]
• Sets the derivative time.

Setting the value to 0 disables the function. (PI action)

• Not available when OUT1 is ON/OFF action
• Setting range: 0 … 300 seconds
• Default: 50 seconds
ARW (Anti-reset windup) setting [ ]
• Sets the anti-reset windup.
• Available only for PID action
• Setting range: 0 … 100 %
• Default: 50 %
OUT1 proportional cycle setting [ ]
• Sets OUT1 proportional cycle.

Not available for ON/OFF action and DC current output type

For the relay contact output type, if the proportional cycle time is decreased, the frequency

of the relay action increases and the life of the relay contact is shortened.

• Setting range: 1 … 120 seconds
• Default: 30 seconds for Relay contact output type,

3 seconds for Non-contact voltage output type

OUT2 proportional cycle setting [

]

• Sets OUT2 proportional cycle.

Not available for ON/OFF action and DC current output type

• Not available when 2. control output (option) is not added or when OUT2 is ON/OFF action
• Setting range: 1 … 120 seconds
• Default: 30 seconds for Relay contact output type,

3 seconds for Non-contact voltage output type

A1 setting [

]

• Sets the action point of A1 output.

Setting the value to 0 or 0.0 disables the function.
(Excluding process high alarm and process low alarm)

• Not available when No alarm action is selected in the A1 action selection
• Setting range: Refer to (Table 5.3-1).
• Default: 0 °C
A2 setting [

]

• Sets the action point of A2 output.

Setting the value to 0 or 0.0 disables the function.
(Excluding process high alarm and process low alarm)

• Not available when option [2AS] or [2AL] is not added or when No alarm action is selected in the

A2 action selection

• Setting range and default value are the same as those of A1 setting.