Operating Instructions Temperature Indicating Controller CS4H / CS4L
V1.1
•
05/2006
- 20 -
Integral time setting [ ]
• Sets the integral time.
Setting the value to 0 disables the function. (PD action)
• Not available when OUT1 is ON/OFF action
• Setting range: 0 … 1000 seconds
• Default: 200 seconds
Derivative time setting [ ]
• Sets the derivative time.
Setting the value to 0 disables the function. (PI action)
• Not available when OUT1 is ON/OFF action
• Setting range: 0 … 300 seconds
• Default: 50 seconds
ARW (Anti-reset windup) setting [ ]
• Sets the anti-reset windup.
• Available only for PID action
• Setting range: 0 … 100 %
• Default: 50 %
OUT1 proportional cycle setting [ ]
• Sets OUT1 proportional cycle.
Not available for ON/OFF action and DC current output type
• For the relay contact output type, if the proportional cycle time is decreased, the frequency
of the relay action increases and the life of the relay contact is shortened.
• Setting range: 1 … 120 seconds
• Default: 30 seconds for Relay contact output type,
3 seconds for Non-contact voltage output type
OUT2 proportional cycle setting [
]
• Sets OUT2 proportional cycle.
Not available for ON/OFF action and DC current output type
• Not available when 2. control output (option) is not added or when OUT2 is ON/OFF action
• Setting range: 1 … 120 seconds
• Default: 30 seconds for Relay contact output type,
3 seconds for Non-contact voltage output type
A1 setting [
]
• Sets the action point of A1 output.
Setting the value to 0 or 0.0 disables the function.
(Excluding process high alarm and process low alarm)
• Not available when No alarm action is selected in the A1 action selection
• Setting range: Refer to (Table 5.3-1).
• Default: 0 °C
A2 setting [
]
• Sets the action point of A2 output.
Setting the value to 0 or 0.0 disables the function.
(Excluding process high alarm and process low alarm)
• Not available when option [2AS] or [2AL] is not added or when No alarm action is selected in the
A2 action selection
• Setting range and default value are the same as those of A1 setting.